Technical data
Automation Panel 9xD - Hygienic design User's manual V 1.80
39
4.1.4.2 SDL3 receiver (5DLSD3.1001-00)
4.1.4.2.1 Overview
The interfaces available on the device or module are numbered for the purpose of clear differentiation.
The numbering used by the operating system may deviate, however.
(3)
(2)
(1)
(5)
(6)
(4)
Figure 3: Overview of interfaces - SDL3 receiver link module
No.
Interface name
Chapter
No.
Interface name
Chapter
1
USB1
4
SDL3 In LEDs
2
USB2
5
Power 24 VDC
3
SDL3 In
6
Grounding
4.1.4.2.2 +24 VDC power supply
Danger!
The device is only permitted to be supplied with a SELV/PELV power supply or with safety extra-low
voltage (SELV) per EN 60950.
The necessary 3-pin connector is not included in delivery; for suitable accessories, see
The device is protected against overload and reverse polarity by a soldered fuse (15 A, fast-acting). If the fuse
is defective (e.g. due to overload), the device must be sent to B&R for repairs. If the polarity is reversed, it is not
necessary to replace the fuse.
Pin
Description
Figure
1
-
2
Functional ground
3
+
•
Reverse polarity protection
•
3-pin
•
Male
1 2 3
Electrical properties
Nominal voltage
24 VDC ±25%, SELV
1)
Nominal current
Max. 3 A
Overvoltage category per EN 61131-2
II
Galvanic isolation
Yes
Uninterruptible power supply
No
1)
EN 60950 requirements must be observed.