Power Panel 65 • 4PP065.0571-P74
Power Panel 65 User's manual V2.21
37
Model number
4PP065.0571-P74
Nominal current
0.45 A
Inrush current
Max. 2.8 A
Power consumption
Typ. 10 W
Electrical isolation
No
Operating conditions
Installation at elevations above sea level
Maximum
3000 m
EN 60529 protection
Back: IP20 (only with an inserted CompactFlash card)
Front: IP65 / NEMA 250 type 4X, dust and sprayed water protection
Environmental conditions
Temperature
Operation
0 to 50°C
Storage
-20 to 70°C
Transport
-20 to 70°C
Relative humidity
Operation
10 to 90%, non-condensing
Storage
T ≤ 40°C: 5 to 90%, non-condensing
T > 40°C: <90%, non-condensing
Vibration
Operation (continuous)
2 to 9 Hz: 1.75 mm amplitude / 9 to 200 Hz: 0.5 g
Operation (occasional)
2 to 9 Hz: 3.5 mm amplitude / 9 to 200 Hz: 1 g
Storage
2 to 8 Hz: 7.5 mm amplitude / 8 to 200 Hz: 2 g / 200 to 500 Hz: 4 g
Transport
2 to 8 Hz: 7.5 mm amplitude / 8 to 200 Hz: 2 g / 200 to 500 Hz: 4 g
Shock
Operation
15 g, 11 ms
Storage
30 g, 15 ms
Transport
30 g, 15 ms
Mechanical characteristics
Housing
Material
Polyester
Front
Multi-layered panel overlay
Dimensions
Width
203 mm
Height
145 mm
Depth
56.5 mm
Weight
5)
0.75 kg
Table 7: 4PP065.0571-P74 - Technical data
1)
Typical service life (at 50% buffer operation: 25°C when device off, 50°C when device on).
Maximum service life in 24h operation (no buffer): 6 years at 25°C, 5 years at 50°C.
Maximum service life when device switched off: 2 years at 25°C, 1 year at 50°C.
2)
Maintenance Controller Extended.
3)
At max. specified ambient temperature: Typ. 50 ppm (4 s); worst case 100 ppm (8 s)
4)
See the help system in Automation Studio under "Communication / POWERLINK / General information / Hardware - IF/LS".
5)
Weight including fasteners and battery (46.5 g) but without an interface module.
2.6.3 Supported interface modules
Support for interface modules is provided starting with the following Automation Runtime versions:
Interface modules
4PP065.IF10-1
4PP065.IF23-1
4PP065.IF24-1
4PP065.IF33-1
Automation Runtime version
A3.01
A3.01
A3.07
A3.01
2.6.4 Diagnostic LEDs
There are four diagnostic LEDs on the back of the PP65.
Information:
The behavior of the Status LED has changed starting with AR J2.96, E3.01 and B3.06.