IGNITION AND ADJUSTMENT WITH
LIQUID FUEL
Before starting up, make sure that:
•
Make sure that the mains voltage corresponds to the manufactu
-
rer's requirements and that all electrical connections made at the
installation site are effected properly as illustrated in our wiring
diagram.
•
Make sure that the combustion products may be freely vented
through the boiler and flue dampers.
•
Check that there is water in the boiler and that the gate valves of
the system are open.
•
Check that all the gate valves fitted on the fuel suction and
return pipes are open; the same applies to any other fuel shut-off
devices.
•
Adjust the air for the ignition flame:
It is recommended to perform the first ignition with the liquid fuel as the
delivery is conditioned by the nozzle.
Then to regulate the gas operate the pressure regulator on the gas
train.
In burners with mechanical cam, after adjusting the gas, it is necessary
to re-check the liquid fuel calibration.
•
Connections to the supply line, to thermostats or pressure swi
-
tches, have been made according to the electrical diagram of the
equipment.
•
There is fuel oil in the tank and water in the boiler.
•
Make sure that the combustion head penetrates into the furnace
to the extent requested by the boiler manufacturer. Check that the
air closure device on the combustion head is in the right position
to guarantee a correct combustion, the air passage between disk
and head must be slightly reduced if a relatively small amount of
fuel is supplied. When the fuel supply is abundant the air passage
must be increased, see chapter "COMBUSTION HEAD ADJUST
-
MENT”.
•
The right type of fuel has been selected.
•
Check that the nozzles fitted on the burner are suitable for the
boiler capacity. If necessary, replace them with suitable ones.
To start the burner proceed as follows:
DANGER / ATTENTION
Prevent operation of the second flame avoiding to connect the
4-pin connector (2nd stage).
•
Adjust the air in the amount presumed to be necessary for the
1st stage ignition using the special cam of the air adjustment
servomotor (indicative value 15° - 20°)
• Turn on the main switch and the one on the control panel.
•
The programmer is activated and it starts carrying out the prede
-
fined program activating the burner devices.The equipment will
start operation as described in the Chapter “DESCRIPTION OF
OPERATION”.
•
When the burner is operating in the 1st stage, adjust the amount
of air necessary to ensure an efficient combustion, see “AIR
ADJUSTMENT ON THE BURNER HEAD” and 0002938170 for
the gas- diesel 1st stage cam adjustment.
•
After adjusting the 1st stage air the burner stops disconnecting
the current from the main switch, the electric circuit commanding
the second stage activation closes connecting the 4-pole connec
-
tor according to the wiring diagram.
•
Adjust the quantity of air necessary for the maximum flow rate
(2nd stage) through the screw/s at the bearing (12).
in a clockwise direction the air flow increases
in an anti-clockwise direction the air flow decreases
TBML_ACC_REG_001
t
Hermal
relaY
calibration
The thermal relay prevents motor failure due to a large increase in
electric absorption, or the lack of single-stage.
For calibrating, please refer to the nominal value of the motor current.
To reset the burner, if the thermal relay trips, press the reset button
(RESET).
DANGER / ATTENTION
The automatic reset may be dangerous thus, when possible, do
not set this function on the thermal relay.
24 / 50
0006160331_202310
ENGLISH
Содержание TBML 80 MC
Страница 2: ......
Страница 45: ...SCHEMI ELETTRICI TBML 50 MC 200 MC 43 50 0006160331_202310 ITALIANO...
Страница 46: ...TBML 50 MC 200 MC 44 50 0006160331_202310 ITALIANO...
Страница 47: ...45 50 0006160331_202310 ITALIANO...
Страница 49: ...TBML 260 MC 360 MC 47 50 0006160331_202310 ITALIANO...
Страница 50: ...TBML 260 MC 360 MC 48 50 0006160331_202310 ITALIANO...
Страница 51: ...TBML 260 MC 360 MC 49 50 0006160331_202310 ITALIANO...
Страница 95: ...WIRING DIAGRAMS TBML 50 MC 200 MC 43 50 0006160331_202310 ENGLISH...
Страница 96: ...TBML 50 MC 200 MC 44 50 0006160331_202310 ENGLISH...
Страница 97: ...45 50 0006160331_202310 ENGLISH...
Страница 99: ...TBML 260 MC 360 MC 47 50 0006160331_202310 ENGLISH...
Страница 100: ...TBML 260 MC 360 MC 48 50 0006160331_202310 ENGLISH...
Страница 101: ...TBML 260 MC 360 MC 49 50 0006160331_202310 ENGLISH...
Страница 103: ......