![baltur TBML 80 MC Скачать руководство пользователя страница 74](http://html1.mh-extra.com/html/baltur/tbml-80-mc/tbml-80-mc_instruction-manual-for-installation-use-and-maintenance_4192510074.webp)
The switch on stage is thus repeated and, if the flame ignites again
normally, the burner starts working again normally, if not (if the flame is
irregular or fails to light completely) the equipment goes automatically
into lock-out (LED 5 comes on).
If the program is interrupted (due to a power supply failure, manual
action or the intervention of the thermostat, etc.) during the pre-wash
stage, the programmer returns to its starting position and will automati-
cally repeat the whole of the burner ignition sequence.
CAUTION / WARNINGS
The selection of the nozzles in function of the desired total flow
rate (2 nozzles in operation) must be made accounting for the
flow rate values that correspond to 12 bar16 bar the diesel
operating pressure. Replacing the nozzles it is possible to
change considerably the ratio between first and second stage.
o
perating
deScription
tbml 210 - 310 ..
The burner's hydraulic circuit is equipped with a solenoid valve and a
by-pass adjusting valve for a smooth vibration-less ignition when ope
-
rating with liquid fuel.
A part of diesel is thus drained only during the first 3-4 seconds of ope
-
ration of the burner. Once ignition is complete, the by-pass solenoid
valve closes and the rate corresponds to the first stage value.
Use a screwdriver on the by-pass adjusting screw located inside the
cap (16), (screw in to increase the pressure) so as to obtain only du
-
ring the ignition stage a pressure of approx. 9 bars, measured by con
-
necting a pressure gauge in position (17).
Correct if necessary the corresponding amount of combustion air by
acting on the electronic equipment settings.
3 6
4
5
2
7
9
1
8
10
Displa
y_TBML_80pn
1
ON / OFF main switch
2
Voltage warning light
3
Fan operation warning light
4
2nd stage LED
5
Transformer ON led
6
1st stage operation warning light
7
Equipment shut-down warning light
8
Equipment release button
9
Fuel loading button
10
Fuel selector switch
0002570210funz210
TBML 210, 310,
16
17
16
Cap for by-pass adjusting screw
17
Pump pressure gauge connection.
22 / 50
0006160331_202310
ENGLISH
Содержание TBML 80 MC
Страница 2: ......
Страница 45: ...SCHEMI ELETTRICI TBML 50 MC 200 MC 43 50 0006160331_202310 ITALIANO...
Страница 46: ...TBML 50 MC 200 MC 44 50 0006160331_202310 ITALIANO...
Страница 47: ...45 50 0006160331_202310 ITALIANO...
Страница 49: ...TBML 260 MC 360 MC 47 50 0006160331_202310 ITALIANO...
Страница 50: ...TBML 260 MC 360 MC 48 50 0006160331_202310 ITALIANO...
Страница 51: ...TBML 260 MC 360 MC 49 50 0006160331_202310 ITALIANO...
Страница 95: ...WIRING DIAGRAMS TBML 50 MC 200 MC 43 50 0006160331_202310 ENGLISH...
Страница 96: ...TBML 50 MC 200 MC 44 50 0006160331_202310 ENGLISH...
Страница 97: ...45 50 0006160331_202310 ENGLISH...
Страница 99: ...TBML 260 MC 360 MC 47 50 0006160331_202310 ENGLISH...
Страница 100: ...TBML 260 MC 360 MC 48 50 0006160331_202310 ENGLISH...
Страница 101: ...TBML 260 MC 360 MC 49 50 0006160331_202310 ENGLISH...
Страница 103: ......