RESIDUAL RISKS
•
Even though the product was designed in compliance with the obli
-
gatory standards, residual risks may still be present during correct
operation. They are signalled on the burner through special Picto
-
grams.
CAUTION
Moving mechanical organs.
CAUTION
Materials at high temperature.
CAUTION
Powered electric panel.
PERSONAL PROTECTIVE EQUIPMENT
•
While working on the burner, use the following safety devices.
ELECTRIC SAFETY WARNINGS
•
Check that the equipment has a suitable ground system, carried out
following safety standards in force.
•
Have qualified personnel check that the electric system is adequate
to equipment maximum power consumption indicated on the plate.
•
For the mains supply connection is required an omnipolar switch
with a contact opening gap equal or above 3 mm in accordance with
current safety regulations (condition of overvoltage category III).
•
Remove the external insulating seal of the supply pipe necessary for
the connection, preventing the cable to touch metal parts.
• The use of any electrically fed components entails complying with
certain fundamental rules, including the following:
-
do not touch the equipment with parts of the body that are wet or
damp or with damp feet;
-
do not pull on electrical cables;
-
do not leave the equipment exposed to atmospheric agents
(such as rain or sun etc.) unless there is explicit provision for
this;
-
do not allow the equipment to be used by children or inexpert
persons;
-
The power supply cable for the equipment must not be replaced
by the user. In case of cable damage, turn the equipment off. To
replace it contact qualified personnel only;
-
If you decide not to use the equipment for a certain period of time
it is advisable to switch off the electrical power supply to all com
-
ponents in the system that use electricity (pumps, burner, etc.).
•
Use regulation-compliant flexible cables EN 60204-1
- in case of PVC sheath, at least type H05VV-F;
-
in case of rubber sheath, at least type H05RR-F; LiYCY
450/750V
- without any sheath, at least type FG7 o FROR, FG70H2R
•
The electric equipment works correctly when the relative humidity
does not exceed the 50% at a maximum temperature of +40° C.
Higher relative humidity are allowed at lower temperatures (e.g. 90
% at 20° C)
•
The electric equipment works correctly at altitudes of up to 1000 m
above the see level.
IMPORTANT
We hereby declare that our gas, liquid and mixed forced drau
-
ght burners respect the minimum requirements of the European
Directives and Regulations and are compliant with European
standards.
A copy of the EC declaration of conformity is supplied with the
burner.
4 / 34
0006160393_202104
ENGLISH
Содержание TBL 1000 ME
Страница 2: ......
Страница 30: ...SCHEMI ELETTRICI TBL 650ME 750ME 1000ME 28 34 0006160393_202104 ITALIANO ...
Страница 31: ...TBL 650ME 750ME 1000ME 29 34 0006160393_202104 ITALIANO ...
Страница 32: ...TBL 650ME 750ME 1000ME 30 34 0006160393_202104 ITALIANO ...
Страница 33: ...TBL 650ME 750ME 1000ME 31 34 0006160393_202104 ITALIANO ...
Страница 34: ...TBL 650ME 750ME 1000ME I1 I2 BA I4 I3 32 34 0006160393_202104 ITALIANO ...
Страница 36: ...34 34 0006160393_202104 ITALIANO ...
Страница 64: ...WIRING DIAGRAMS TBL 650ME 750ME 1000ME 28 34 0006160393_202104 ENGLISH ...
Страница 65: ...TBL 650ME 750ME 1000ME 29 34 0006160393_202104 ENGLISH ...
Страница 66: ...TBL 650ME 750ME 1000ME 30 34 0006160393_202104 ENGLISH ...
Страница 67: ...TBL 650ME 750ME 1000ME 31 34 0006160393_202104 ENGLISH ...
Страница 68: ...TBL 650ME 750ME 1000ME I1 I2 BA I4 I3 32 34 0006160393_202104 ENGLISH ...
Страница 70: ...34 34 0006160393_202104 ENGLISH ...
Страница 71: ......