BURNER CONNECTION TO THE BOILER
For burner handling, use certified chains or ropes suitable for the bur
-
ner weight using the anchoring points (21).
•
Hook with suitable handling ropes or chains into the burner eye
-
bolts (32).
HEAD UNIT ASSEMBLY
The combustion head is packaged separately from the body of the
burner.
Anchor the head unit to the boiler door as follows:
• Position the insulating seals on the sleeve (13).
•
Fasten the head unit flange (15) to the boiler (1) by means of the
stud bolts,washers and the nuts provided (7).
CAUTION / WARNINGS
Completely seal the space between the burner sleeve and the
hole in the refractory material inside the boiler door with sui
-
table material.
ASSEMBLY OF VENTILATION SYSTEM
•
The burner has an ambidextrous hinge opening for easy access to
the combustion head with fitted burner.
•
After installing the head group on the boiler, assemble the two hin
-
ges (12) (17), on the buffer, using the screws (21) and the corre
-
sponding washers, without fully tightening them.
•
Position the ventilating body (2) where the two hinges are located.
• Insert pin (10), then lock it using the nuts (23) and the correspon-
ding washers, taking care that the abutting surfaces of the two hin
-
ges are perfectly in contact with the corresponding surfaces of the
scroll.Do not tighten the nuts (23) excessively, as this may make
hinge rotation difficult.
•
Tighten the centring pin (20) on the fan flange, opposite to the hin
-
ge side.
•
Keeping the chains anchored to the eyebolts, turn the ventilating
body and place the fan flange in contact with the buffer flange,
making sure that the pin (20) is inserted in the corresponding hole.
•
Close the burner using the screws (11) and the corresponding wa
-
shers.
•
Once the ventilating body is connected to the head unit, start the
final tightening of the four screws fixing the hinges, then release the
lifting chains or ropes.
• Connect the tie rod (15) to the gas adjustment throttle control lever
(26).
IMPORTANT
Every time the burner has to be opened, it is necessary to di
-
sconnect gas solenoid valves connectors first.
ACOUSTIC SHROUD
If it is necessary to reduce the sound pressure level, install a sui
-
table acoustic shroud. (see technical price list and contact the dealer)
).Baltur).
0002936670
15
7
13
1
21
32
12
17
21
21
10
23
23
20
0002937700
2
11
26
15
0002937710
11 / 30
0006160266_202106
ENGLISH
Содержание TBG 900 MC
Страница 2: ......
Страница 28: ...SCHEMI ELETTRICI TBG 800 MC 900 MC 1100 MC 26 30 0006160266_202106 ITALIANO...
Страница 29: ...TBG 800 MC 900 MC 1100 MC 27 30 0006160266_202106 ITALIANO...
Страница 30: ...TBG 800 MC 900 MC 1100 MC 28 30 0006160266_202106 ITALIANO...
Страница 31: ...TBG 800 MC 900 MC 1100 MC 29 30 0006160266_202106 ITALIANO...
Страница 58: ...WIRING DIAGRAMS TBG 800 MC 900 MC 1100 MC 26 30 0006160266_202106 ENGLISH...
Страница 59: ...TBG 800 MC 900 MC 1100 MC 27 30 0006160266_202106 ENGLISH...
Страница 60: ...TBG 800 MC 900 MC 1100 MC 28 30 0006160266_202106 ENGLISH...
Страница 61: ...TBG 800 MC 900 MC 1100 MC 29 30 0006160266_202106 ENGLISH...
Страница 63: ......