SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
7
9
8
4
H
P
6
10
3
1
0002900740N2
IMPORTANT
For any components missing in the pipes, comply with current
regulations.
IMPORTANT
Total length of pipeline, including vertical length.
Deduct 0.25 m for each elbow or gate.
1 Fuel tank.
3 Mesh filter.
4 Burner.
6 Suction pipe.
7 Burner return pipe.
8 Automatic fuel shut-off device with burner at stop.
9 One-way valve.
10 Foot valve.
Value "P" max. 3.5 m
H Measurement between minimum oil level and pump axis.
H
Inner pipe diameter
Ø 14 mm
Total length of each pipe
m
m
1
30
1,5
35
2
35
2,5
40
3
40
INTAKE SUPPLY SYSTEM
3
7
10
4
H
6
1
0002900740N3
IMPORTANT
For any components missing in the pipes, comply with current
regulations.
IMPORTANT
Total length of pipeline, including vertical length.
Deduct 0.25 m for each elbow or gate.
1 Fuel tank.
3 Mesh filter.
4 Burner.
6 Suction pipe.
7 Burner return pipe.
10 Foot valve.
H Measurement between minimum oil level and pump axis.
H
Total L.
Meters
Meters
Ø 14 mm
Ø 16 mm
0,5
26
45
1
22
38
1,5
19
31
2
14
25
2,5
11
19
15 / 30