Battery Equalization

Due to the hazardous nature of equalization (the intentional overcharging of batteries to remove sulfation from the battery 

plates) we strongly recommend that the process be done at the dock with a voltage-adjustable shorepower charger. If it is 

absolutely impossible to do so, equalization can be done with the alternator and regulator by doing the following:

1. 

In Advanced programming, Pra, change the following values.

2. 

Cl to a voltage above the desired equalize voltage.

3. 

AHL to a voltage above the desired equalize voltage.

4. 

Bv to the desired equalize voltage.

5. 

Blc to the desired equalize time.

6. 

Disconnect ALL battery temperature sensors.

7. 

YOU MUST MONITOR THE BATTERIES DURING EQUALIZE PROCESS!

8. 

Once the equalization is complete, activate the regulator’s basic programming and reset the battery program 

mode to UFP, and allow the program to save. Once saved, access the basic programming mode again and reset 

for the desired battery program.

WARNING: EQUALIZATION IS A MANUAL PROCESS WITH POTENTIAL DANGERS.

DO NOT LEAVE SYSTEM UNATTENDED.

(F1c) Float Time. 

Controls minimum time in Float Mode before entering Calculated Float. Standard value set is .3 

hours (18 minutes). Settings are from 6 minutes to 6 hrs. Adjustable in .1 hrs (6 minute) increments.

(ALL) Low Voltage Limit.

 Allows user control of regulator’s low voltage limit. Spans between 10 volts and Fv. 

Dropping below ALL causes Dash Lamp to turn on. Default is 12.7 volts in .1 volt increments.

(FbA) Field Threshold - Bulk and Absorption.

 Controls the field output threshold required to cycle from Bulk 

to Absorb and Absorb to Float. Factory set at 65% of field output. Raising “FbA” shortens calculated bulk and 

absorption charge time. Adjusted in 1% increments. Span of adjustment is 16% to 96%. 

(FFL) Field Threshold - Float to Absorption. 

Controls the field output threshold required to cycle from float to 

absorption charging modes. Factory set at 65%. Raising “FFL” increases calculated float charge time. Adjusted in 

1% increments. Span of adjustment is 16% to 96%. 

(AL1) Alternator Temperature Threshold.

 Controls the Alternator over temperature set point. Requires MC-TS-A 

temperature sensor to be connected to the Alt. Temp. #1 and/or Alt. #2 temperature sensor terminals. Preset at 

100°C. Spans from 60-128°C. Adjustable in 1°C increments. 

(b1L) Battery Temperature Threshold.

 Controls the Battery over temperature set point. Requires MC-TS-B 

temperature sensor to be connected to the Bat. Temp. #1 and or Bat. #2 temperature sensor terminals. Preset at 

52°C. Spans from 42-56°C. Adjustable in 1°C increments.

(SLP) Slope Voltage Correction.

 Adjusts the voltage (in millivolts) the regulator uses when monitoring battery 

temperature sensing. Can be custom adjusted to meet the needs of unique battery technologies. Consult with 

battery manufacturer for specific slope voltage recommendations. Spans from 0 to 8.3 millivolts per degree Celsius. 

Default is 6.0 mV/°C. Adjustable in 0.1mV/°C increments. 

Содержание MAX CHARGE MC-614

Страница 1: ...thing or jewelry which could become entangled in your motor or other machinery prior to installing regulator 3 Wear ANSI approved safety eye wear and protective gear 4 DO NOT attempt to modify the reg...

Страница 2: ...tors distance from alternator distance from inverters transmitters and other sources of RF noise convenient access and readability of the display The regulator wiring harness is 54 inches long providi...

Страница 3: ...E 10 DATA TX 11 DATA RX 12 STATOR IN 13 TACHOMETER OUT 14 BAT 2 TEMP 15 BAT 2 TEMP 16 AUX 1 LAMP 17 DASH LAMP MC 614 Regulator Terminal Layout Magnetic Reed Switch 17 16 15 14 13 12 11 10 9 8 7 6 5 1...

Страница 4: ...ug or a ring terminal depending on the alternator s field terminal connection Attach the field wire to the alternator s field terminal Install Alternator Temperature Sensor The optional Alternator Tem...

Страница 5: ...e alternator stator output it will be necessary to determine the number of poles in the alternator in order to properly adjust your tachometer Most Balmar alternators feature 12 pole rotors and stator...

Страница 6: ...gulator s programming tool A small magnet embedded in the top of the screwdriver s handle allows the user to activate the magnetic reed switch By holding the magnet to the RED dot located at the end o...

Страница 7: ...ltage for a set time period specified by the battery program selected Factory set values are 13 9 volts for 0 3 hours 18 minutes and are adjustable with Av and A1c respectively See page 14 7 Calculate...

Страница 8: ...Flooded Halogen Systems Lithium Yes Yes Yes Yes Yes Balmar Alternator Models 6 Series Alternators 70A 150A Yes Yes Yes Yes Yes Yes AT Series Alternator 165A 200A Yes Yes Yes Yes 9 Series Large Case A...

Страница 9: ...ER 55 C FACTORY DEFAULT E21 BATTERY 2 TOO HOT OVER 55 C FACTORY DEFAULT E22 ALTERNATOR TOO HOT OVER 107 C E24 VOLTAGE REGULATOR TOO HOT OVER 90 C E33 BATTERY SENSE DIS CONECTED E41 FIELD VOLTAGE TOO H...

Страница 10: ...he reed switch Within the basic and advanced programming instructions activation of the reed switch will be described by the following actions TOUCH RELEASE Indicates the action of contacting and imme...

Страница 11: ...cifics Your battery manufacturer may supply you with a C rate for charging and discharging The maximum amount of charging current your battery can safely handle is determined by multiplying the C Rate...

Страница 12: ...ax b 2 90 Field Max b 3 85 Field Max b 4 80 Field Max b 5 75 Field Max b 6 70 Field Max b 7 65 Field Max b 8 60 Field Max b 9 55 Field Max AL2 2nd Alternator Sensor Mode b2 2nd Battery Sensor Mode Sd...

Страница 13: ...0 INDICATES BLM OFF b 1 INDICATES BLM SETTING 1 FIELD REDUCTION 5 b 2 INDICATES BLM SETTING 2 FIELD REDUCTION 10 b 3 INDICATES BLM SETTING 3 FIELD REDUCTION 15 b 4 INDICATES BLM SETTING 4 FIELD REDUC...

Страница 14: ...croll upward or downward To reverse the direction of scroll 1 REMOVE the magnet from the reed switch 2 Wait for the mode indicator to be displayed 3 TOUCH HOLD when the mode indicator is displayed The...

Страница 15: ...it Allows user control of regulator s low voltage limit Spans between 10 volts and Fv Dropping below ALL causes Dash Lamp to turn on Default is 12 7 volts in 1 volt increments FbA Field Threshold Bulk...

Страница 16: ...on Low Battery Voltage 12 8V Adjustable with ALL See Page 12 High Battery Voltage 15 5V Adjustable with AHL See Page 11 High Alternator Temperature 225 F Adjustable with AL1 See Page 12 Requires insta...

Страница 17: ...An amp meter and a battery hydrometer with a thermometer are also helpful diagnostic tools Voltage Regulator Testing Set your voltmeter to 12VDC and connect the negative lead to the BLACK ground wire...

Страница 18: ...t test Testing the actual output of the alternator is known as Full Field Testing This can be accomplished by jumping a positive 12VDC current to the field terminal at the rear of the alternator This...

Страница 19: ...plication maintenance or modification or b any misuse contrary to the instructions provided with the product or c loss or d malfunctions caused by other equipment or e acts of God Examples of conditio...

Страница 20: ...he world To Find a CDI distribution partner visit www cdielectronics com Both Balmar and CDI Products are manufactured in our ISO 9000 Certified Factory in Huntsville Alabama Please read carefully All...

Отзывы: