Install Battery #1 Temperature Sensor

The optional Battery Temperature Sensor (MC-TS-B) enables the regulator 

to monitor for changes in ambient battery temperature, and adjust charging 

voltages to suit. The MC-TS-B sensor assmbly includes a 20-foot cable, a 

sensing attachment lug and positive and negative regulator plug-in connec-

tors. To install the MC-TS-B:
1.  Connect the sensor lug to the battery negative post closest to the cen-

ter of the battery bank. Extend sensor cable to the regulator

2.  Connect  the  positive  and  negative  female  connectors  to  the  Battery 

temperature sensors on the regulator (#10 is NEGATIVE. #11 is POSI-

TIVE). NOTE: Wire terminals must match the polarity of the regulator 

connection pins (red wire to positive terminal and black wire to negative 

terminal).

Install Positive Battery Sense Wire

Included with the MC-612’s wiring harness kit is a fused wiring pigtail which 

features a ring terminal at one end and a butt connector at the other. In the 

center is a 1-Amp ATC-type fuse and fuse holder. This wire must be con-

nected at the #12 Positive Battery Sense terminal A female quick connect 

plug has been pre-attached on the terminal #12 pin. To complete installa-

tion of the sense circuit:
1.  Identify the favored location for battery sensing. In most instances, the 

positive output of the alternator, the common side of a battery switch, or the positive post of the battery being charged 

will work best. If the batteries are connected to a  battery isolator, the positive sense wire must be connected to the 

battery side of the isolator, preferably at the larger of the battery banks. 

2.  Attach the included wiring pigtail with 1-amp fuse to a length of wire of sufficient to reach from the regulator to the 

desired sensing location. If the length of the wire run between the regulator and the sensing location is 8’ or less, a 

16-gauge wire is satisfactory. If the wire run exceeds 8’, increase the wire size to 14 gauge.

3.  Remove the female 1/4” spade terminal from the terminal #12 pin. Crimp the spade terminal to the sense wire and 

reconnect the spade to the #12 terminal pin.

Data TX and RX Terminals (#13 and #14)

Are currently for factory use only, and are capped to protect against accidental connection.

Install WHITE Stator-In And Tach-Out Wires

The alternator’s stator output provides the electrical pulse needed to drive the tachometer. The MC-612-DUAL provides 

regulated tach output when the WHITE stator wire is connected to the regulator’s Stator In (#15 in diagram) terminal and 

the outfeed wire to the electric tachometer is connected to the Tach Out terminal (#16 in diagram). 
Most Balmar alternators feature 12-pole rotors and stators, though, in some cases, the pole count may be 14. See alterna-

tor manual for specifics. See your tachometer manual for adjustment instructions.

Install Battery #2 / Alternator #2 Temperature Sensor

Your Max Charge MC-612-DUAL voltage regulator can accomodate either alternator or battery temperature sensing on 

terminals #17 and #18, depending on your preference. When controlling two alternators with the MC-612-DUAL, the use 

of a secondary alternator temperature sensor enables the regulator to respond to over-temperature conditions at the 

second alternator. Used in conjunction with an optional MC-TS-B battery temperature sensor, the regulator can monitor 

temperature at a secondary battery bank, and respond to a battery over-temperature condition by discontinuing charging.
To install a secondary temperature sensor:
1.  Select the optional sensor that best fits your application.
2.  Connect the temperature sensor to the secondary alternator or battery bank following the directions provided for the 

primary alternator or battery temperature sensor.

3.  Plug the sensor cable BLACK (negative) wire to #17 and RED (positive) wire to #18. Select the program setting in the 

voltage regulator’s basic program mode that corresponds to your sensing selection. 

CAUTION: 

Reversing the polarity of the terminal connections on any of the alternator or battery temperature 

sensors can result in invalid sensing and potential damage to alternators, regulator and/or batteries.

- 5 -

Содержание MAX CHARGE MC-612-DUAL

Страница 1: ...ternators are being used to charge the same large battery bank The MC 612 DUAL provides two field output connectors two power input connectors and two system ground connections making it pos sible to...

Страница 2: ...rom inverters transmitters and other sources of RF noise convenient access and readability of the display The regulator wiring harness is 54 inches long providing a three to four foot radius for mount...

Страница 3: ...BATTERY Temperature Sensor MC TS A Sensor lug connects to negative battery post enabling regula tor to monitor and respond to battery temperature condition USE CARE TO ENSURE POSITIVE AND NEGATIVE WI...

Страница 4: ...switch or to the wire in the existing engine wiring loom that delivers switched voltage from the ignition switch In some cases an oil pressure switch may be used to activate the regulator In either ca...

Страница 5: ...e 1 4 spade terminal from the terminal 12 pin Crimp the spade terminal to the sense wire and reconnect the spade to the 12 terminal pin Data TX and RX Terminals 13 and 14 Are currently for factory use...

Страница 6: ...gramming features Included with the regulator is a small screwdriver that doubles as the regulator s programming tool A small magnet embedded in the tip of the screwdriver s handle allows the user to...

Страница 7: ...ds the bulk charge time by an additional six minutes and compares real time to target values This will re occur until all values are met 5 Ramps down to Absorption voltage 6 Absorption Charge Regulato...

Страница 8: ...code Indicates temperature setpoint for ambient alternator and battery temperatures Followed by degrees celsius Indicates in millivolts the voltage value used to control voltage compensation for batt...

Страница 9: ...AgL Optima OPS as well as a factory default program UFP and a program for systems with voltage sensitive halogen equipment HAL Programming can be accomplished whenever the regulator is activated Syste...

Страница 10: ...16 and 17 Programming For Secondary Alternator OR Regulator Temperature Sensor The regulator allows the user to select between the use or a second battery temperature sensor or a second alternator tem...

Страница 11: ...ues for that mode will begin to scroll in the opposite direction Continue to HOLD until the desired value is displayed 4 REMOVE the magnet from the RED dot The mode indicator will be displayed again f...

Страница 12: ...indicated Field Threshold Bulk To Absorption Controls the criteria the regulator uses to determine how hard the alternator has to be working to stay in calculated bulk charging mode Factory set at 67...

Страница 13: ...at s capable of providing a signal to a user supplied and installed audible or visual alert to indicate the following while the regulator is in operation Small Engine Mode is activated Regulator is at...

Страница 14: ...tery Sense wire and there is zero or an unexpected voltage reading at the BLUE wire contact our technical support staff at 360 435 6100 or e mail us at balmar balmar net If all voltages at the regulat...

Страница 15: ...tery side of the isolator if an isolator is in use Use a SHIELDED alligator clip for post attachment Unintentional contact between the alligator clip and the alternator case could result in damage to...

Страница 16: ...eplacement In order to expedite warranty claims more efficiently BALMAR asks that prior to returning a defective product for repair you call their customer service department for a warranty return aut...

Отзывы: