www.balluff.com
BTS M30E0-_ _ _-H0001-S04G
Infrared Temperature Sensor
21
9
Configuring the Digital Outputs
english
9.5
Teach-in
The upper switching thresholds of the digital outputs can be taught independently of each other. A static teach-in
procedure is used with two teach points. The switching threshold results, after successful teaching, from the setting
of both teach points.
Teach-in
1.
Use [
↵
] to confirm teach-in and start the teach-in
routine.
⇒
The screen then guides you through the teach-in
routine.
2.
Align the sensor with the object and use [
↵
] to
confirm.
⇒
Teach point 1 (TP1) is learned.
3.
Remove the object from the detection range and use
[
↵
] to confirm.
⇒
Teach point 2 (TP2) is learned.
Note
TP2 (background) must be at least 1% of the detection range less than TP1 (object).
The upper switching threshold is set between the object
(TP1) and the background (TP2). The lower switching
threshold is set by 1% of the detection range below the
upper switching threshold.
If the switching thresholds are not within the detection
range or TP2 (background) is not less by 1% than TP1
(object), the teach-in procedure is ended with an error
indication and the old switching thresholds remain in
effect.
4.
Check the taught switching thresholds and confirm with [
↵
] .
⇒
The switching thresholds are now saved and in effect.
Содержание BTS M30E0-PSB-H0001-S04G
Страница 1: ...deutsch Betriebsanleitung english User s Guide BTS M30E0 UUI H0001 S04G BTS M30E0 PSB H0001 S04G ...
Страница 2: ...www balluff com ...
Страница 3: ...BTS M30E0 UUI H0001 S04G BTS M30E0 PSB H0001 S04G Betriebsanleitung deutsch ...
Страница 49: ...BTS M30E0 UUI H0001 S04G BTS M30E0 PSB H0001 S04G User s Guide english ...
Страница 95: ......