www.balluff.com
35
english
Switching Speed Monitoring Input
With
Switching Speed Monitoring Input
, the internal binary
signal source can be selected.
Input
contains a list of the
internal binary signals.
Value
Meaning
0x0002 (2)
Digital Input Pin 2
0x0003 (3)
Switching Counter Limit not reached
0x0004 (4)
Switching Counter Limit reached
0x0005 (5)
Switching Counter Limit exceeded
0x0007 (7)
Switching Counter Reset
0x0008 (8)
Signal Delay Channel 1
0x0009 (9)
Signal Delay Channel 2
0x000A (10)
Signal Delay Channel 3
0x000B (11)
Signal Delay Channel 4
0x0010 (16)
Switching Speed ok
0x0011 (17)
Switching Speed too low
0x0012 (18)
Switching Speed too high
0x0014 (20)
Switching Speed Reset
0x0015 (21)
Short Circuit Pin 4
0x0016 (22)
Short Circuit Pin 2
0x0017 (23)
Undervoltage
0x0018 (24)
Overvoltage
0x0023 (35)
Humidity Bad
0x0027 (39)
Transducer Enable
0x002D (45)
Optical Transmitter Error
0x002F (47)
System Error
0x0034 (52)
PDout Invalid
0x0037 (55)
Inclination Alarm Status
0x0041 (65)
Lifetime Extreme
0x004B (75)
Vibration Alarm Status
0x004E (78)
Temperature Status Customer Limits
0x004F (79)
Temperature Status Device Limits
0x0063 (99)
Logic block result 1
0x0064 (100)
Logic block result 2
0x0065 (101)
Logic block result 3
0x0066 (102)
Logic block result 4
Tab. 6-9: Signal Speed Monitoring – Speed Monitoring Input
6
Secondary Device Functions (continued)
Switching Speed Monitoring Mode
With
Switching Speed Monitoring Mode
, the current mode
of the counter function can be selected.
Value
Meaning
Description
0x00 (0) Deactivated
Deactivated
0x01 (1) Speed
Speed monitoring
Tab. 6-10: Signal Speed Monitoring – Speed Monitoring Mode
Speed Upper Limit High
In combination with
Speed Upper Limit Low
, it forms a
threshold value with hysteresis for the
too high
status.
Speed Upper Limit Low
In combination with
Speed Upper Limit High
, it forms a
threshold value with hysteresis for the
too high
status.
Speed Lower Limit High
In combination with
Speed Lower Limit Low
, it forms a
threshold value with hysteresis for the
too low
status.
Speed Lower Limit Low
In combination with
Speed Lower Limit High
, it forms a
threshold value with hysteresis for the
too low
status.
Speed Monitoring Startup Delay
With
Startup Delay
, the time for the startup delay can be
set. The startup delay begins after the supply voltage is
switched on. During the startup delay, speed monitoring
has no function. Speed monitoring starts after the startup
delay has elapsed. The value represents the time in
seconds. The value range is between 0x00 (0) and 0xFF
(255). A value of 0x00 (0) represents no start delay.
BOS R254K-UUI-LS10-S4
Photoelectric Sensors
Содержание BOS R254K-UUI-LS10-S4
Страница 1: ...deutsch Konfigurationsanleitung english Configuration Guide BOS R254K UUI LS10 S4 ...
Страница 2: ...www balluff com ...
Страница 3: ...BOS R254K UUI LS10 S4 Konfigurationsanleitung deutsch ...
Страница 4: ...www balluff com ...
Страница 88: ......
Страница 89: ...BOS R254K UUI LS10 S4 Configuration Guide english ...
Страница 90: ...www balluff com ...