www.balluff.com
BIS V-6106 Ethernet/IP™
Processor Unit
65
The operating states of the identification system, the Ethernet/IP interface and the IO-Link
master are displayed using LEDs.
Figure 7:
Function Indicators
1
Ready device (RD)
6
Link/Activity EIP 1 (L/A)
2
Module status (MS)
7
RD R/W head
3
Network status (NS)
8
COM R/W head
4
Display
9
Service/IO-Link
5
Link/Activity EIP 2 (L/A)
LED
Color
Status
Meaning
RD
Green
Off
Device is not ready for operation
On
Device is ready for operation
L/A
Green
Off
No link
Static on
Link detected, no data transmission
Flicker
Data transmission
MS
Red/green
Off
Device not turned on
Green
Static on
Device is ready for operation
Flashes
Stand-by: Device not configured
Red
Static on
Severe, fatal error
Flashes
Simple, non-fatal error (e.g. an incorrect configuration)
Red/green
Flashes
Self test: Device is undergoing a self test after being
switched on
NS
Red/green
Off
Device not turned on or there is no IP address
Green
Static on
Connected: Device has an existing connection to the
master
Flashes
No connection: Device has no existing connection, IP
address is not available
Red
Static on
Doubled IP address: Device identified that its IP address
is already being used.
Flashes
Connection timeout
Red/green
Flashes
Self test: Device is undergoing a self test after being
switched on
7.3 Function
Indicator
Overview of
display elements
Device LEDs
7
Device
Functions