Single Value Teach
With
Single Value Teach
, the switching point (setpoint) is
defined via a teach point. Moreover, this is a static process,
i.e., the measurement value is constant during the teach
phase. The teach process is performed independently for
each switching point in Two-Point Mode or Window Mode.
Fig. 5-7:
High
SP1
Low
Workflow:
1. Teach SP1
Measured value
Switch output
Single Value Teach in Single Point Mode
Fig. 5-8:
High
SP1
SP2
Low
Workflow:
1. Teach SP2
2. Teach SP1
Measured value
Switch output
Single-Value Teach in Two-Point Mode
Two Value Teach
With
Two-Value Teach
, the switching point (setpoint) is
defined via two teach points. The average value of the two
teach points defines the setpoint. This is a static process
as well, i.e., each teach point is defined statically. The
teach process can be performed independently for each
switching point in Two-Point Mode or Window Mode. The
teach process is concluded with the Apply command; this
is only possible if each of the two teach points has been
taught. Alternatively, the teach process can be interrupted
with a Cancel command. All incomplete teach point pairs
are thereby lost.
Fig. 5-9:
High
SP1
TP1 TP2
Low
Workflow:
1. Teach SP1 TP1
2. Teach SP1 TP2
3. Teach Apply
Measured
value
Switch output
Two Value Teach in Single Point Mode
5
Primary Device Functions (continued)
Fig. 5-10:
High
SP1
TP1
TP1 TP2
TP2
SP2
Low
Workflow:
1. Teach SP2 TP1
2. Teach SP2 TP2
3. Teach Apply (optional)
4. Teach SP1 TP1
5. Teach SP1 TP2
6. Teach Apply
Measured
value
Switch output
Two-Value Teach-In Two-Point Mode
Dynamic Teach (Smart Sensor Profile Spec.)
With this process, no static teach points are recorded,
unlike with the previous methods; rather, multiple
measurement values are recorded over a defined period of
time. Measurement value acquisition is started with the
Dynamic Teach SP1 Start
system command and ended
with
Dynamic Teach SP1 Stop
. If all recorded
measurement values were in the valid detection range, the
switching point calculation is started. For this purpose, the
minimum and maximum values are determined. The
average value of these two extrema is used to form the
new switching point (setpoint). The maximum acquisition
time is 5 minutes. After 5 minutes without a Stop
command, the event 0x8DC0
Teach Timeout
is set.
Fig. 5-11:
High
SP1
Low
Workflow:
1. Dynamic Teach SP1 Start
2. Dynamic Teach SP1 Stop
Recorded measurement values
Measured
value
Switch output
Dynamic Teach in Single-Point Mode
Fig. 5-12:
High
SP1
SP2
Low
Workflow:
1. Dynamic Teach SP1 Start
2. Dynamic Teach SP1 Stop
3. Dynamic Teach SP2 Start
4. Dynamic Teach SP2 Stop
Recorded measurement values
Measured
value
Switch output
Dynamic Teach in Two-Point Mode
BCS Q40BBAA-PIM20C-EP _ _ _ -GS04
Capacitive Proximity Switches
Содержание BCS Q40BBAA-PIM20C-EP-GS04 Series
Страница 1: ...BCS Q40BBAA PIM20C EP___ GS04 deutsch Konfigurationsanleitung english Configuration Guide...
Страница 2: ...www balluff com...
Страница 3: ...BCS Q40BBAA PIM20C EP___ GS04 Konfigurationsanleitung deutsch...
Страница 4: ...www balluff com...
Страница 87: ...BCS Q40BBAA PIM20C EP___ GS04 Configuration Guide english...
Страница 88: ...www balluff com...
Страница 171: ......