13
13
E
Parametering, Addressing
Station Address
setting
The station address under which the unit is accessed on the bus can be assigned through
the sliding switch S1. Each address shall be assigned only once.
Open the cover of the processor, see 39 for BIS C-602 or 51 for BIS C-622.
The sliding switch S1 is binary coded. The setting of the station address is carried out
according to the scheme shown in the table: yes = switch right, no = switch left.
The address 85 is set in the following figure.
Sliding switch S1
(with cover opened)
no yes
Station
Address
Switch S1
1
2
3
4
5
6
7
2
0
2
1
2
2
2
3
2
4
2
5
2
6
0
not allowed
1
yes
no
no
no
no
no
no
2
no
yes
no
no
no
no
no
3
yes
yes
no
no
no
no
no
4
no
no
yes
no
no
no
no
5
yes
no
yes
no
no
no
no
...
85
yes
no
yes
no
yes
no
yes
...
123
yes
yes
no
yes
yes
yes
yes
124
no
no
yes
yes
yes
yes
yes
125
yes
no
yes
yes
yes
yes
yes
126
no
yes
yes
yes
yes
yes
yes
127
not allowed
Slide switch S1/8
must
remain set to the "yes" position.
C6_2-019_641365_0506-e.p65
14
14
E
Parametering
Parametering Bytes
User-Parameter-Bytes
(continued)
For parametering all 4 bytes must always be transferred in Hex. Only the bits mentioned
may be changed. No guaranty will be given for the proper functioning of the BIS C-6_2
if any of the other bits are changed.
1st byte
2nd byte
3rd byte
4th byte
Hex
00
80
00
02
Binary
0 0 0
0
0
0 0 0
1 0 0
0
0 0 0 0
0 0 0 0 0 0 0 0
0
0
0
0
0 0
1
0
bit 4
bit 5
bit 5 bit 2
bit 5
bit 6
bit 7
bit 8
The bits which serve for parametering have the following functions:
1st byte, bit 5
,
activate CRC_16 data checking:
0 = no
1 = yes
CRC_16 data checking activated.
1st byte, bit 4
,
display the selected read/write head in the header of the input buffer:
0 = no
1 = yes
read/write head 1 selected: "KN" in the header of the input buffer = 0,
read/write head 2 selected: "KN" in the header of the input buffer = 1.
Important:
"KN" and "IN" use the same bit in the header. "IN" has always priority!
2nd byte, bit 5
,
dynamic mode (for effects on the read/wirte times, see
35/36):
0 = no
A read/write request is denied with Error No. 1 if no data carrier is within
the permitted read/write zone.
1 = yes
The read/write request is buffered and only executed when a data
carrier is recognized.
☞
Please note:
All commands
affecting Head 2 are
invalid in all versions
for a single read/
write head.