7.CONTROL MODE
The air conditioner will enter defrosting as long as any of the three conditions is satisfied. .
7.1 Defrosting procedures:
Both the compressor and outdoor fan motor are interrupted.
50 seconds later, the 4-way valve turns off.
5 seconds later, the compressor gets started.
Defrosting (the compressor runs) starts. The longest defrosting time is
Y minutes(Y is 7 for 2501,11 for both 3301 and 3201,13 for 4801).
3 minutes after defrosting starts (the compressor runs), the value of the
compressor current is read. From then on, if the compressor current is above
1.2 A higher than the current at the end of the first 3 minutes, the system
quits defrosting 1 minutes later.
30 seconds later, the 4-way valve turns on.
5 seconds later, compressor starts.
3 seconds later, outdoor fan starts.
Defrosting ends.
8. Fan mode
When select the fan mode,only both the indoor fan and flap operate in a preset mode. If the fan speed is set to
“automatic”, the fan runs at the low speed.
9.
Flap control
9.1 Press the up and down flap button, the flap's position is switched over between the 8 statuses, i.e. automatic flap,
flap orientation where the flap plate opens to 6 positions 1, 2, 3, 4, 5, 6 from down to up, and flap swing.
9.2 Automatic flap: In the heating mode, the flap swings between position 1 and position 4; In the cooling or
dehumidification mode, the flap swings between position 3 and position 6; In the fan mode, the flap is located at
to position 5.
9.3 Flap orientation: The flap is set at a certain position by using the remote controller.
9.4 Flap swing: The flap swings between position 1 and position 6.
9.5 The default status is the “automatic flap”.
9.6 When powered on and off for the first time, the flap plate turns to the maximum angle to ensure that the flap is
closed; When the unit starts, the flap plate moves to the maximum angle, and returns to the preset position after
the flap is completely closed.
10. Man-machine communication
10.1The indoor control unit has two thermal sensors for detecting the room temperatures, one is installed in the
remote controller, and the other at the air intake of the indoor unit. The default air outlet setting is subject to the
remote controller's
35
The air conditioner will enter defrosting as long as any of the three conditions is satisfied. .
7.1 Defrosting procedures:
Both the compressor and outdoor fan motor are interrupted.
50 seconds later, the 4-way valve turns off.
5 seconds later, the compressor gets started.
Defrosting (the compressor runs) starts. The longest defrosting time is
Y minutes(Y is 7 for 2501,11 for both 3301 and 3201,13 for 4801).
3 minutes after defrosting starts (the compressor runs), the value of the
compressor current is read. From then on, if the compressor current is above
1.2 A higher than the current at the end of the first 3 minutes, the system
quits defrosting 1 minutes later.
30 seconds later, the 4-way valve turns on.
5 seconds later, compressor starts.
3 seconds later, outdoor fan starts.
Defrosting ends.
8. Fan mode
When select the fan mode,only both the indoor fan and flap operate in a preset mode. If the fan speed is set to
“automatic”, the fan runs at the low speed.
9.
Flap control
9.1 Press the up and down flap button, the flap's position is switched over between the 8 statuses, i.e. automatic flap,
flap orientation where the flap plate opens to 6 positions 1, 2, 3, 4, 5, 6 from down to up, and flap swing.
9.2 Automatic flap: In the heating mode, the flap swings between position 1 and position 4; In the cooling or
dehumidification mode, the flap swings between position 3 and position 6; In the fan mode, the flap is located at
to position 5.
9.3 Flap orientation: The flap is set at a certain position by using the remote controller.
9.4 Flap swing: The flap swings between position 1 and position 6.
9.5 The default status is the “automatic flap”.
9.6 When powered on and off for the first time, the flap plate turns to the maximum angle to ensure that the flap is
closed; When the unit starts, the flap plate moves to the maximum angle, and returns to the preset position after
the flap is completely closed.
10. Man-machine communication
10.1The indoor control unit has two thermal sensors for detecting the room temperatures, one is installed in the
remote controller, and the other at the air intake of the indoor unit. The default air outlet setting is subject to the
remote controller's
Содержание KF-25GWE
Страница 14: ......
Страница 15: ......
Страница 16: ......
Страница 17: ......
Страница 22: ......
Страница 23: ......
Страница 24: ......
Страница 25: ......
Страница 53: ...12 PARTS LIST KFR 33GE 52 KF R 25GE KFR 2501GE KFR 3301GE KF 34GE KFR 3201GE...
Страница 54: ...12 PARTS LIST KFR 33WE KF R 25WE KFR 2501WE KFR 3301WE KF 34WE KFR 3201WE 53...
Страница 55: ...12 PARTS LIST KF 5002WE 54...
Страница 62: ...12 PARTS LIST KF 4801WE 2 3 4 5 6 7 14 15 17 18 16 1 8 9 10 11 20 12 21 13 19 22 23 24 25 26 61...