Section 1
General Information
Receiving & Installation 3-33
MN715
Electronic Pot 2 Wire Operating Mode
Provides speed Increase and Decrease inputs to allow EPOT operation with 2 wire
inputs. The opto inputs can be switches as shown in Figure 3-33 or logic signals from
another device. The values of the preset speeds are set in the Level 1 Preset Speeds
block, Preset Speed #1 or Preset Speed #2.
Figure 3-33 EPOT, 2 Wire Control Connection Diagram
See recommended terminal
tightening torques in Section 6.
8
9
10
11
12
13
14
15
16
17
Enable
Forward Run
Reverse Run
Speed Select #1
Speed Select #2
Accel/Decel Rate Select
External Trip
Opto In Common
Analog GND
Analog Input 1
Pot Reference
Analog Input +2
Analog Input -2
Analog Out 1
Analog Out 2
1
2
3
4
5
6
7
Increase
Decrease
J4
Refer to Figure 3-36.
Programmable Output
Programmable Output
J4-8
CLOSED allows normal control operation.
OPEN disables the control and motor coasts to a stop.
J4-9
CLOSED starts motor operation in the Forward direction.
OPEN motor decels to stop (depending on Keypad Stop mode).
J4-10
CLOSED starts motor operation in the Reverse direction.
OPEN motor decels to stop (depending on Keypad Stop mode).
Note: Closing both J4-9 and J4-10 at the same time will reset a fault condition.
J4-11
Selects speed command as defined in the Speed Select Table 3-15.
J4-12
Selects speed command as defined in the Speed Select Table 3-15.
J4-13
CLOSED selects ACC / DEC / S-CURVE group 2.
OPEN selects ACC / DEC / S-CURVE group 1.
J4-14
Momentary CLOSED increases motor speed while contact is closed.
J4-15
Momentary CLOSED decreases motor speed while contact is closed.
J4-16
If J4-16 is connected, you must set Level 2 Protection block, External Trip to
“ON” to activate the opto input.
CLOSED allows normal control operation.
OPEN causes an external trip fault. The control will disable and the motor
coasts to a stop. An external trip fault is displayed (also logged in the fault log).
5K
W
Command Pot or
0-10VDC
Table 3-15 Speed Select Table
J4-11
J4-12
Command
Open
Open
Electronic Pot
Closed
Open
Analog Input (Level 1, Input, Command Select)
Open
Closed
Level 1, Preset Speeds, Preset Speed #1
Closed
Closed
Level 1, Preset Speeds, Preset Speed #2
Содержание -W
Страница 1: ...SERIES 15H Inverter Control Installation Operating Manual 2 01 MN715 ADJUSTABLE SPEED DRIVE ...
Страница 51: ...3 40 Receiving Installation MN715 ...
Страница 128: ...Appendix C Appendix C 1 MN715 ...
Страница 131: ...MN715 Series 15H Inverter Control ...