Troubleshooting 5-3
MN715
How to Access the Fault Log
When a fault condition occurs, motor operation stops and a fault code is displayed on
the Keypad display. The control keeps a log of the last 31 faults. If more than 31 faults
have occurred, the oldest fault will be deleted from the fault log. To access the fault log,
perform the following procedure:
Action
Description
Display
Comments
Apply Power
Logo display for 5 seconds.
Display mode showing Local
mode voltage, current &
frequency status.
No faults present. Local keypad
mode. If in remote/serial mode,
press local for this display.
Press DISP key
Press DISP to scroll to the Fault
Log entry point.
Press ENTER key
Display first fault type and time
fault occurred.
Typical display.
Press
key
Scroll through fault messages.
If no messages, the fault log exit
choice is displayed.
Press RESET key
Return to display mode.
Display mode stop key LED is on.
How to Clear the Fault Log
Use the following procedure to clear the fault log.
Action
Description
Display
Comments
Apply Power
Logo display for 5 seconds.
Display mode showing output
frequency.
Display mode.
Press DISP key
Press DISP to scroll to the Fault
Log entry point.
Press ENTER key
Displays most recent message.
Press SHIFT key
Press RESET key
Press SHIFT key
Press ENTER key
Fault log is cleared.
No faults in fault log.
Press
or
key
Scroll Fault Log Exit.
Press ENTER key
Return to display mode.
Содержание -W
Страница 1: ...SERIES 15H Inverter Control Installation Operating Manual 2 01 MN715 ADJUSTABLE SPEED DRIVE ...
Страница 51: ...3 40 Receiving Installation MN715 ...
Страница 128: ...Appendix C Appendix C 1 MN715 ...
Страница 131: ...MN715 Series 15H Inverter Control ...