Troubleshooting 6-5
MN1924
Symptom
Check
Motor is under control, but
when moved to a position and
then back to the start it does
not return to the same position.
Verify that the NextMove ESB and drive are correctly
grounded to a common earth point.
(Servo outputs only)
Check:
H
all encoder channels are free from electrical noise;
H
they are correctly wired to the controller;
H
when the motor turns, the two square wave signals
are 90 degrees out of phase. Also check the
complement signals.
Ensure that the encoder cable uses shielded twisted pair
cable, with the outer shield connected at both ends and
the inner shields connected only at the NextMove ESB
end.
(Stepper outputs only)
The motor is not maintaining
synchronization with the NextMove ESB drive output
signals due to excessive acceleration, speed or load
demands on the motor.
Check that the acceleration, speed and load are within the
capabilities of the motor.
6.2.4 WorkBench v5
Symptom
Check
The Spy window does not
update
The system refresh has been disabled. Go to the Tools,
Options menu item, select the System tab and then
choose a System Refresh Rate (500ms is recommended).
Содержание Nextmove ESB
Страница 1: ...NextMove ESB Motion Controller MOTION CONTROL Installation Manual 1 04 MN1924...
Страница 2: ......
Страница 6: ...iv Contents MN1924...
Страница 16: ...www supportme net 3 4 Basic Installation MN1924...
Страница 42: ...www supportme net 4 26 Input Output MN1924...
Страница 57: ...www supportme net Operation 5 15 MN1924 Figure 28 The NextMove ESB servo loop...
Страница 88: ...www supportme net A 4 General MN1924...
Страница 94: ...Index MN1924...
Страница 96: ...Comments MN1924 Thank you for taking the time to help us...
Страница 97: ......