Figure 4-3 Maximum Output Frequency vs PWM Frequency
50
100
200
300
400
500
600
700
800
900
1.00KHz
8.00KHz
16.00KHz
HZ
It is recommended that the PWM frequency parameter be set
to approximately16 times the maximum output frequency of
the control. The greater the ratio, the more sinusoidal the
output current waveform will be.
OUTPUT FREQUENCY
PWM FREQUENCY
1000
Note: The output current rating of the control must be derated for high PWM
frequency operation as follows:
Standard Constant Torque and Standard Variable Torque: Linearly
derate to 10% between 2.5 and 5.0KHz (10% derating at 5.0KHz).
Quiet Constant Torque and Quiet Variable Torque: Linearly derate to
30% between 8.0 and 16KHz (30% derating at 16KHz).