Section 1
General Information
Receiving & Installation 3-11
MN722
Wire Size and Protection Devices
Table 3-5 lists the recommended wire size and the breaker or fuse size for each control.
The specified wire sizes and protective devices are based on the maximum output power
possible from the control. If the control is programmed for an operating zone that
provides less output power, the wire size and the rating of the protective devices may be
reduced but must meet NEC and other applicable codes.
Table 3-5 Wire Size and Protection Devices - 230 VAC Controls
Control O tp t
Inp t Breaker
Inp t F se
Wire Ga ge
Control Output
P
R ti
Input Breaker
Input Fuse
Wire Gauge
p
Power Rating
p
Fast Acting
Time Delay
AWG
mm
2
10
35A
40A
35A
10
10
15
50A
60A
50A
8
10
20
60A
80A
60A
4
25
25
80A
100A
80A
4
25
30
100A
125A
100A
3
30
40
125A
150A
125A
1
50
50
150A
200A
150A
2/0
70
Note: All wire sizes based on 75
°
C copper wire, 3% line impedance. Higher temperature smaller gauge wire may be
used per NEC and local codes. Recommended fuses/breakers are based on 25
°
C ambient, maximum
continuous control output current and no harmonic current.
Table 3-6 Wire Size and Protection Devices - 460 VAC Controls
Control O tp t
Inp t
Inp t F se
Wire Ga ge
Control Output
P
R ti
Input
B
k
Input Fuse
Wire Gauge
p
Power Rating
p
Breaker
Fast Acting
Time Delay
AWG
mm
2
10
20A
25A
17.5A
12
4
15
25A
30A
25A
10
6
20
30A
40A
30A
8
10
25
40A
50A
40A
8
10
30
45A
60A
45A
6
16
40
60A
80A
60A
4
25
50
70A
100A
75A
4
25
60
90A
125A
90A
2
35
75
125A
150A
125A
1/0
54
100
150A
200A
150A
2/0
70
125
175A
250A
175A
2/0
70
150
200A
300A
200A
4/0
120
200
250A
350A
250A
(2)1/0
(2)54
250
350A
450A
350A
(2)3/0
(2)95
300
400A
500A
400A
(2)4/0
(2)120
350
500A
600A
500A
(3)4/0
(3)120
400
600A
800A
600A
(3)250 mcm
(3)125
450
600A
800A
600A
(3)250 mcm
(3)125
Note: All wire sizes based on 75
°
C copper wire, 3% line impedance. Higher temperature smaller gauge wire may be
used per NEC and local codes. Recommended fuses/breakers are based on 25
°
C ambient, maximum
continuous control output current and no harmonic current.
Содержание 22H series
Страница 1: ...SERIES 22H Line Regen AC Flux Vector Control Installation Operating Manual 9 97 MN722 VECTOR DRIVE...
Страница 5: ...Section 1 General Information iv Table of Contents MN722...
Страница 105: ...Section 1 General Information 5 22 Troubleshooting MN722...
Страница 109: ...Section 1 General Information 6 4 Manual Tuning the Series 22H Control MN722...
Страница 137: ...Section 1 General Information A 8 Appendix A MN722...
Страница 138: ...Appendix B Appendix B 1 MN722...