Section 1
General Information
3-12 Receiving & Installation
MN722
Single Phase Operation
Single phase operation is not possible for Series 22H Line Regen Vector Controls.
Operating the Control at a Reduced Input Voltage
Series 22H Controls use a DC Bus regulation technique that provides full output voltage
(240VAC for 230VAC Controls; or 480VAC for 460VAC controls) for the full input voltage
range. However, at reduced input voltages the output current of the control may have to
be derated. Table 3-7 lists the % derating of the output current for various motor voltage
ratings and input power voltage levels to the control.
Table 3-7 Output Current Derating at Reduced Input Voltages (2.5KHz PWM)
Input Voltage
% of Output Current after Derating
230VAC Control
460VAC Control
240/480VAC Motor
230/440VAC Motor
208/400VAC Motor
180VAC
340VAC
77%
84%
93%
190VAC
360VAC
82%
89%
98%
208VAC
400VAC
90%
99%
100%
230VAC
440VAC
100%
100%
100%
240VAC
480VAC
100%
100%
100%
For example:
A 460VAC Control that has a 400VAC input line can provide 90% of the rated current to a
480VAC motor. In the Section 6 specifications we find our example 10HP control is
ZD22H410-EL has a continuous current rating of 15 Amps. The derated current can be
calculated as follows: 15A x 90% = 13.5A derated value.
Содержание 22H series
Страница 1: ...SERIES 22H Line Regen AC Flux Vector Control Installation Operating Manual 9 97 MN722 VECTOR DRIVE...
Страница 5: ...Section 1 General Information iv Table of Contents MN722...
Страница 105: ...Section 1 General Information 5 22 Troubleshooting MN722...
Страница 109: ...Section 1 General Information 6 4 Manual Tuning the Series 22H Control MN722...
Страница 137: ...Section 1 General Information A 8 Appendix A MN722...
Страница 138: ...Appendix B Appendix B 1 MN722...