Section 1
General Information
B-2 Appendix
MN715
Table B-1 Parameter Block Values Level 1
Continued
Level 1 Blocks - Continued
Block Title
Parameter
P#
Adjustable Range
Factory
User
Setting
INPUT
OPERATING MODE
1401
Keypad
Standard Run
15 Speed
Fan Pump 2Wire
Fan Pump 3Wire
Serial
Process CTRL
3SPD ANA 2WIRE
3SPD ANA 3WIRE
EPOT – 2WIRE
EPOT – 3WIRE
Keypad
COMMAND SELECT
1402
Potentiometer
0-10 VOLTS
0-5 VOLTS
4-20 mA
EXB PULSE FOL
10V EXB
4-20 mA EXB
3-15 PSI EXB
Tachometer EXB
None
Potentio-
Meter
ANA CMD INVERSE
1403
OFF, ON
OFF
ANA CMD OFFSET
1404
-20.0 to +20.0%
(where
±
0.5V=
±
20%)
0.0 %
ANA CMD GAIN
1405
80.0% to 120%
100.0%
CMD SEL FILTER
1406
0-6
3
PWR UP MODE OP
1407
Primary Mode, Last, Local
Primary
Mode
OUTPUT
DIGITAL OUT #1
1501
Ready
Zero Speed
Ready
DIGITAL OUT #2
1502
At Speed
At Set Speed
Overload
Zero Speed
DIGITAL OUT #3
1503
Keypad Control
Fault
Drive On
At Speed
DIGITAL OUT #4
1504
Drive On
Reverse
Process Error
Fault
ZERO SPD SET PT
1505
0-MAX Speed
6.00Hz
AT SPEED BAND
1506
0-20Hz
2.00Hz
SET SPEED POINT
1507
0-MAX Speed
60Hz