Section 1
General Information
Programming & Operation 4-11
MN715
Security System Access Timeout Parameter Change
Action
Description
Display
Comments
Apply Power
Keypad Display shows this
opening message.
Logo display for 5 seconds.
If no faults and programmed for
LOCAL operation.
Display mode. Stop LED on.
Press PROG key
Enter program mode.
Press
or
key
Scroll to Level 2 Blocks.
Press ENTER key
Access Level 2 Blocks.
Press
or
key
Scroll to the Security Control
block.
Press ENTER key
Access the Local Security block.
Press
key
Scroll to the Access Timeout
parameter.
Press ENTER key
Attempt to access the Access
Timeout parameter.
represents blinking cursor.
Press
key
Use
key to change value.
Example: 8999.
Note: Ignore the 5 digit number to
the right (example: 23956).
Press ENTER key
Save Access Code parameter
Security code entered is correct.
All parameters may be changed.
Press SHIFT key.
Move cursor right on digit.
Access Timeout can be any value
between 0 and 600 seconds.
Press
key 3 times
Change the 0 to 3.
Example: 30 seconds.
Press ENTER key
Save value.
P: will change to L: after you
return to Display mode for longer
than the time specified in the
Access Time parameter.
Press DISP key
Return to Display mode.
Typical display mode.
Note: Please record your access code and store it in a safe place. If you cannot
gain entry into parameter values to change a protected parameter, please
contact Baldor. Be prepared to give the 5 digit code located on the lower right
side of the Keypad Display at the Enter Code prompt.