5-4 Troubleshooting
MN715
Initialize New Software EEPROM
After a new EEPROM is installed, the control will automatically initialize the new software
version and memory locations as if “STD Settings” was selected. If you need to initialize
the control to the 50Hz / 400Volts” settings, use the “
Initialize New Software
EEPROM”
procedure in section 4.
Table 5-1 Fault Messages
FAULT MESSAGE
DESCRIPTION
Invalid Base ID
Failure to determine control horsepower and input voltage configuration from the Power
Base ID value in software.
NV Memory Fail
Failure to read or write to non-volatile memory.
Param Checksum
Parameter Checksum error detected.
Low INIT Bus V
Low bus voltage detected on startup.
HW Desaturation
High output current condition detected (greater than 400% of rated output current). On B2
size controls, a desat error can indicate any of the following: low line impedance, brake
transistor failure or internal output transistor overtemperature.
HW Surge Current
High output current condition detected (greater than 250% of rated output current).
HW Ground Fault
Ground Fault detected (output current leakage to ground).
HW Power Supply
Control Board power supply failure detected.
Hardware Protect
A general hardware fault was detected but cannot be isolated.
1 MIN Overload
Peak output current exceeded the 1 minute rating value.
3 SEC Overload
Peak output current exceeded the 3 second rating value.
Overcurrent
Continuous current limit exceeded.
BUS Overvoltage
High DC Bus voltage.
Bus Undervoltage
Low DC Bus voltage condition detected.
Heat Sink Temp
Control heatsink exceeded upper temperature limit. For size B2 controls, this fault may
indicate the main heatsink or the gate drive circuit board is too hot.
External Trip
Connection between J4-16 and J4-17 is open.
New Base ID
Control board detected a change in the Power Base ID value in software.
REGEN RES Power
Excessive power dissipation required by Dynamic Brake Hardware.
Line REGEN
Fault in Line REGEN converter unit - Series 21H Line REGEN Inverter control.
EXB Selection
Expansion board not installed to support the selected Level 1 Input Block, Command
Select parameter.
Torque Proving
Unbalanced current in the three phase motor leads.
Unknown FLT Code
Microprocessor detected a fault that is not identified in the fault code table.
µ
P RESET
A software watchdog timer has reset the processor because a process has timed out.
FLT Log MEM Fail
Corrupt data in fault log (may occur on older systems only).
Current SENS FLT
Failure to sense phase current.
Bus Current SENS
Failure to sense bus current.