Section 1
General Information
Receiving & Installation 3-37
MN715
Figure 3-38 Opto-Input Connections (Using External Supply)
See recommended terminal
tightening torques in Section 6.
*
User VCC = 10 - 30VDC External Power Source
*
User VCC (-)
*
User VCC (+)
Opto Inputs Closing to Ground
Opto Inputs Closing to +VCC
15
16
17
39
40
Opto In #8
Opto In #9
8
9
10
11
12
13
14
J4
Opto In #1
Opto In #2
Opto In #3
Opto In #4
Opto In #5
Opto In #6
Opto In #7
*
User VCC (+)
*
User VCC (-)
15
16
17
39
40
Opto In #8
Opto In #9
8
9
10
11
12
13
14
J4
Opto In #1
Opto In #2
Opto In #3
Opto In #4
Opto In #5
Opto In #6
Opto In #7
Opto-Isolated Outputs
Two programmable opto isolated outputs are available at terminals J4-19 through J4-22.
See Figure 3-39. Each output may be programmed to represent one output condition.
The output conditions are defined in Section 4 of this manual.
The opto isolated outputs may be configured for sinking or sourcing 60 mA each, as
shown in Figure 3-39. However, both must be configured the same. The maximum
voltage from opto output to common when active is 1.0 VDC (TTL compatible). The
equivalent circuit for the opto isolated outputs is shown in Figure 3-40.
If the opto outputs are used to directly drive a relay, a flyback diode rated at 1A, 100 V
(IN4002 or equivalent) minimum should be connected across the relay coil.
Each opto output is programmed in the Output programming block.
Figure 3-39 Opto-isolated Output Configurations
See recommended terminal tightening torques in Section 6.
Using Internal Supply
(Sinking the Relay Current)
Optional
Customer
Supplied
Relays &
Diodes
Using Internal Supply
(Sourcing the Relay Current)
Using External Supply
(Sinking the Relay Current)
Using External Supply
(Sourcing the Relay Current)
Optional Customer Supplied
10VDC to 30VDC Source
17
18
19
20
24Com
39
41
42
+24VDC
Optional
Customer
Supplied
Relays &
Diodes
17
18
19
20
39
41
42
+
-
Optional
Customer
Supplied
Relays &
Diodes
17
18
19
20
24Com
41
42
+24VDC
Optional
Customer
Supplied
Relays &
Diodes
17
18
19
20
39
41
42
Optional Customer Supplied
10VDC to 30VDC Source
+
-
39
Содержание 15H SERIES 15H
Страница 1: ...SERIES 15H Inverter Control Installation Operating Manual 2 01 MN715 ADJUSTABLE SPEED DRIVE...
Страница 51: ...3 40 Receiving Installation MN715...
Страница 128: ...Appendix C Appendix C 1 MN715...
Страница 131: ...MN715 Series 15H Inverter Control...