Masoneilan SVI FF Bench Quick Start Manual
=
|
13
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
a. Measuring and recording the full mechanical travel.
b. Checking Valspeq specs for required full travel.
c. Calculating the stop adjustment %:
Open Stops Adjustment (OSA) is defined as the ratio between required and full
travel:
OSA = (required travel)*100/(full mechanical travel).
For example: (3.8" required travel)*100/(4.8" full mechanical travel) = 79 % stop
adjustment.
A sample procedure is:
1. Click the
Find Stops
tab and entering
79%
in
Open Stop Adjustment
field.
2. Click the
Download Selected Tabs
icon.
3. Note the change in
Position
%.
4. Click
Trend
menu and
Position Setup
, enter 100% in
Manual Setpoint
field and hit
the Tab key. Red box in Figure 11.
Figure 11 Trend
5. Check the travel scale on actuator to make sure 100% in DTM matches 100% on the
travel scale.
Once all procedures are complete, you must put the SVI FF into
Manual or Auto mode before returning to operations.