INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-403A
2 - 5
Make connections to the TU after it is mounted in the field ter-
mination panel. To install the cable follow these steps:
1. Verify IMASM02 and IMAMM03 are unplugged from the
MMU backplane.
2. Insert the hooded end of an NKTU01/11 cable into the
module mounting unit backplane slot assigned to the slave
module. The cable should latch securely in place. Card edge
connector P3 of the slave module connects to this end of the
cable.
3. Insert the male 36 pin connector end of the NKTU01/11
cable from the first slave module into the P1 connector of the
TU. The cable should latch securely in place.
4. Insert the male 36 pin connector end of the NKTU01/11
cable from the second slave module into the P2 connector of
the TU. The cable should latch securely in place.
5. For nonredundant IMAMM03 operation, insert the hooded
end of the NKTU01/11 cable into the module mounting unit
backplane slot assigned to the master module. The cable
should latch securely in place.
6. Insert the male 36 pin connector end of the NKTU01/11
cable from the master module into the P4 connector of the
NTAI02. The cable should latch securely in place.
7. If this is the (second or above) interconnected TU, insert the
male 36 pin connector end of the NKAI01/11 cable into the P5
connector of the TU. The cable should latch securely in place.
8. If this is the (second or above) interconnected TU, insert the
male 24 pin connector end of the NKAI01/11 cable into the P4
connector of the next interconnected TU closer to the master
module. The cable should latch securely in place.
9. Slide each IMASM02 into the MMU until the module is fully
seated and the faceplate is flush with the front of the rack.
CAUTION
Remove modules from their module mounting unit slots before
installing or removing a cable assigned to that slot. Failure to
do so could result in damage to the module.
ATTENTION
Retirer le module de son emplacement dans le chassis de
montage des modules avant d'installer ou de retirer un câble
assigne a cet emplacement. Un manquement à cette procédure
pourrait endommager le module.