REPAIR/REPLACEMENT PROCEDURES
REPLACEMENT PROCEDURES
4 - 2
I-E96-403A
®
To replace an NTAI02 termination unit:
1. Turn
off
the INFI 90 cabinet power.
NOTE: The I/O power supplies providing the power to the TU may
not be located in the same cabinet as the TU. Make sure to turn
off
power to any external supplies providing I/O power.
2. Remove terminal block covers.
3. Label and remove all field wiring from the terminal blocks.
4. Label and disconnect all cables connected to the TU.
5. Label and disconnect system I/O power and ground from
the terminals.
6. Remove the two screws securing the TU to the field termi-
nation panel and remove the TU.
7. Insert the tabs of the replacement termination unit into the
proper slots of the field termination panel standoff and slide it
into position.
8. Secure the termination unit circuit board to the field termi-
nation panel with two screws. Do not overtighten.
9. Remove terminal block covers from the replacement TU.
10. Connect all field wiring removed in Step 3.
11. Connect the system I/O power wires and system ground
wires removed in Step 5 and verify connections.
12. Connect all cables removed in Step 4.
13. Install terminal block covers.
14. Energize the cabinet power supply that provides power to
the TU.
15. Turn on any external power supplies providing I/O power.
16. Calibrate the replacement TU by following the procedure in
the IMAMM03 product instruction. Refer to Section 1 for the
current manual identification number.
Replacing Fuses
Fuse F1 is shipped installed on the TU. It is a 0.25 amp, 250
volt (Bailey part number 194776A12500). The fuse is in fuse
holder F1.