INTRODUCTION
I-E96-621A
D - 1
APPENDIX D - TERMINATION MODULE (NICL01)
CONFIGURATION
INTRODUCTION
The INLIM03 can use the NICL01 for termination. Table
lists the terminal assignments for the loop input/output con-
nections. Table
lists BNC connector assignments. Figure
provides jumper settings associated with cable type. Fig-
ure
shows twinax cable connections for NICL01.
NOTE: Twinax cables connect to the terminals. Coax cables con-
nect to the BNC connectors.
CAUTION
Ensure that the end marked J1 is connected to P1 on the
NICL01, and J2 is connected to the LIM. Failure to do so could
result in module damage (see Figure
ATTENTION
S'assuree que L'extremite identifiee par J1 est reliee a P1 du
module NICL01 et que J2 est reliee au module LIM. Sinon, les
nodules pouiraient etre endommages (voir la figure
Table D-1. NICL01 Terminal Assignments
TB1
Terminal
Assignments
TB2
Terminal
Assignments
TB3
Terminal
Assignments
1
Gound
4
Power System Status 1
25
Loop 1 Out, Shield
2
Common
5
Power System Status 2
26
Loop 1 Out, -
3
+ 24 VDC
6
Loop 2 In, +
27
Loop 1 Out, +
7
Loop 2 In, -
28
Loop 1 In, Shield
8
Loop 2, Shield
29
Loop 1 In, -
9
Loop 2 Out, +
30
Loop 1 In, +
10
Loop 2 Out, -
31
no connection
11
Loop 2 Out, Shield
32
no connection
Table D-2. D-2. BNC Connector
Assignments
BNC
Number
Assignments
J1
Loop 1 In
J2
Loop 1 Out
J8
Loop 2 In
J9
Loop 2 Out