INSTALLATION
INSTALLING THE INTERFACE MODULES
3 - 10
I-E96-621A
®
Installing the INPCT01
To install the PCT:
1. Verify the PCT slot assignment in the MMU.
2. Attach the hooded end of the cable (NTKU01 for the
NTMF01; NKTM01 for the NIMF01) to the MMU backplane
cable connector opening for the PCT. The other end of the cable
attaches to the termination unit or backplane of the Termina-
tion Mounting Unit (NTMU01).
3. Guide the top and bottom edges of the circuit card along
the top and bottom rails of MMU.
4. Slide the module into the slot; push the module until the
front panel is flush with the top and bottom of the MMU frame.
5. Turn the two captive latches a half turn to lock the module
in place.
Installing the INLIM03 and INBTM01
The LIM and BTM should be installed as a pair in adjacent
slots. To install the LIM/BTM:
1. Verify the MMU slot assignments for the modules.
2. Attach the hooded end of the cable (NKLS03 for NTCL01;
NKLS04 for the NICL01) to the MMU backplane cable connec-
tor opening for the LIM. The other end of the cable attaches to
the termination unit or TMU backplane.
3. Connect one end of the Bailey supplied ribbon cable (DMA
cable) to the P4 connector on the LIM. Connect the other end of
the DMA cable to the P4 connector on the BTM (see Figures
and
4. Guide the top and bottom edges of both circuit cards along
the top and bottom rails of adjacent slots in the MMU.
WARNING
Disconnect power before installing dipshunts for slave mod-
ules on the MMU backplane (slave expander bus). Failure to do
so could result in severe or fatal shock.
AVERTISSEMENT
Couper l'alimentation avant d'installer les dipshunts sur la
plaque arrlere du chassis de montage de modules (MMU).
Toute negligence a cet egard constitue un risque de choc pou-
vant entrainer des blessures graves, voire moretlles.