OPERATING PROCEDURES
SECURITY FUNCTIONS
4 - 6
I-E96-621A
®
Utilities
The utilities menu shown in Figure
is available to the user
by attaching a diagnostic monitor to port 1. Enable this option
through the PCT dipswitches. To use the INPCT01 utilities:
Select Item 1 -
TALK90
1. A menu of all CIU commands appear on the screen (see
Figure
2. The first command must be the CIU RESTART command to
put the PCI on-line. To execute this command, select com-
mand 19 from the TALK90 menu. Enter the following values
for questions asked:
KEY - 0
WATCHDOG - 0
OPTIONS - 10
REPLY DELAY - 0
INTERRUPT INTERVAL - 0
Figure 4-4. Utilities Menu
UTILITIES MENU, PCT01/LSM02 REVISION E_O
COPYRIGHT (C) 1990 BAILEY CONTROLS COMPANY
1
TALK90
2
DEFINE PASSWORDS
3
COMMAND/REPLIES
4
STATISTICS
5
MONITOR MODE
6
DEBUG MESSAGES
7
READ MEMORY
8
CPU UTILILZATION
9
MESSAGE RATES
T
TIMESYNC ACCURACY
SELECT OPTION:
T00412A