OPERATING PROCEDURES
SECURITY FUNCTIONS
I-E96-621A
4 - 11
3. Selecting: 2—> Disconnects displays the current rate and
prompts the operator to enter a newrate. This option sets the
rate the PCI disconnects points and the number of disconnects
packed per message. The default setting is one message every
two seconds with 20 disconnects per message.
Select Item T -
TimeSync accuracy
This option sets the accuracy of the Plant Loop time synchro-
nization message output by the PCT as a result of the SET
SYSTEM DATE AND TIME command. Selecting this option dis-
plays the current time synchronization accuracy and prompts
the operator to enter a new rating. The rating indicates the
accuracy (lack of drift) of the host's clock device where:
0 = no clock (lowest accuracy rating)
3 = default
6 = Low accuracy battery-backed clock
9 = high accuracy battery-backed clock
12 = satellite clock (highest accuracy rating)
Figure 4-8. Message Rate Adjustment Menu
MESSAGE RATE ADJUSTMENT MENU
1
ESTABLISHES
2
DISCONNECTS
3
QUIT
SELECT OPTION:
T00408A