INTRODUCTION
SPECIFICATIONS
I-E96-621A
1 - 5
SPECIFICATIONS
Ports
2 Full duplex serial data EIA standard RS-232-C Type Z
(A Bailey defined binary interchange)
One optional IEEE-488 Parallel
Memory
PCT
LIM
BTM
UVR0M: 128 kbytes
RAM: 512 kbytes
NVRAM: 8 kbytes
RAM: 2 kbytes
ROM: 4 kbytes
RAM: 32 kbytes
ROM: 16 kbytes
Power Requirements
PCT
LIM
BTM
+5 VDC at 6 amps; 30 watts nominal
+15 VDC at 37 mA; 0.55 watts nominal
-15 VDC at 18 mA; 0.27 watts nominal
+5 VDC at 2.0 amps: 10 watts nominal
±
15 VDC at 80 mA; 1.2 watts nominal
+ 5 VDC at 1.0 amps; 5 watts nominal
+ 15 VDC at 150 mA; 2.25 watts nominal
- 15 VDC at 120 mA; 1.80 watts nominal
Communication Rates
50 to 19,200 baud (user-selectable)
Mounting
Occupies four slots in standard INFI 90 Module Mounting Unit (MMU).
Occupies five slots with the optional INPBS01.
Environmental
Electromagnetic/Radio
Frequency Interference
Ambient Temperature
Relative Humidity
Altitude
Air Quality
Values are not available at this time. Keep cabinet doors closed. Do not
use communication equipment any closer than two meters from the
cabinet.
0
o
to 70
o
C (32
o
F to 158
o
F)
0 to 95% up to 55
o
C (131
o
F) (non-condensing)
0 to 45% at 70
o
C (158
o
F) (non-condensing)
Sea level to 3 Km (1.86 miles)
Non-corrosive
Certification
All INPCI02 modules have been individually CSA certified for use as
process control equipment in an ordinary (non-hazardous)environment.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE