INSTALLATION
SPECIAL OPERATIONS
3 - 6
I-E96-211A
®
SPECIAL OPERATIONS
The special operations feature which allows you to configure
the MFC to do a one-time special operation rather than enter-
ing its normal mode of operation. Steps 1 through 8 explain
how to set the MFC for special operations and reset it for nor-
mal operation. Table
shows the switch settings and
explains each special operation.
Special operation 2 should be done as the first step of installa-
tion. If you are installing the MFC in an INFI-NET or Superloop
environment, do special operation 4 next. If you desire time
stamping, next do special operation 6.
To reverse INFI-NET protocol or time stamping, do operation 2
again.
1. Set switch U72 pole 1 to the 1 position.
2. Set poles 2 through 6 per Table
3. Insert the module in its slot in the module mounting unit
(refer to Installing Modules).
4. When the special operation is complete, the Status LED
turns red and LEDS 1 through 6 illuminate.
5. Remove the module.
6. Reset pole 1 to the 0 position.
Table 3-5. Switch U72 Special Operations
Pole
Value
1
128
2
64
3
32
4
16
5
8
6
4
7
2
8
1
Special
Operation
Description
1
0
0
0
0
0
0
0
0
Reserved. Do not use. If you use this
setting your module may not operate
properly.
1
1
0
0
0
0
0
0
1
Reserved for future options. Not used at this
time.
1
1
0
0
0
0
0
2
Initialize NVRAM configuration space.
1
1
1
0
0
0
0
0
3
Reserved. Do not use. If you use this
setting your module may not operate
properly.
1
0
0
1
0
0
0
0
4
INFI-NET protocol enable. This allows the
MFC to take advantage of INFI-NET/
Superloop capabilities.
1
1
0
1
0
0
0
0
5
Permit segment modification (allows
change to segment scheme configured with
Function Code 82 specification S1).
1
0
1
1
0
0
0
0
6
Enable time stamping. This operation
instructs the MFC to generate time
information with point data. It is applicable
only to INFI-NET/Superloop systems.