INSTALLATION
SETUP FOR COMMUNICATION HIGHWAY ENVIRONMENT
I-E96-211A
3 - 5
SETUP FOR COMMUNICATION HIGHWAY ENVIRONMENT
INFI-NET/Superloop
To configure the MFC for use in the INFI-NET/Superloop envi-
ronment, follow Steps 1 through 4.
1. Set dipswitch U72 poles 1 and 4 in the OFF (open/logic 1).
All other poles must be in the ON (closed/logic 0) position.
Doing so does not modify the configuration.
2. Reset the module. The Status LED turns red and LEDs 1
through 6 illuminate.
3. Set dipswitch U72 back to its original (or permanent
setting).
4. Reset the module.
Plant Loop
To configure the MFC for use in the Plant Loop environment,
follow Steps 1 through 5.
1. Set dipswitch U72 with poles 1 and 3 in the OFF (open/
logic 1) position to perform a default MFC format operation. All
remaining poles must be in the ON (closed/logic 0) position.
NOTE: This Step deletes the configuration and all files.
2. Reset the module. The Status LED turns red and LEDs 1
through 6 illuminate.
3. Set dipswitch U72 to its original (or permanent setting).
4. Reset the module.
5. Reload plant loop environment configuration.
Table 3-4. Memory Board Jumpers
Jumper
Configuration
Use
JP1 - JP10 Jumper pins 2 and 3
Selects 8K x 8 NVM
JP11
Removed
Not used - The MFC will NOT function
properly with this jumper in place.
P12
Jumper pins 2 and 3
Selects 256K ROM