background image

CONFIGURATION

FUNCTION CODES

4 - 6

  

I-E96-211A

®

Function Code 82 - Segment Control

Function Code 82, Segment Control, is permanently assigned
to block 15 and occupies the next four consecutive blocks. The
Segment Control block is used to divide the set of function
blocks into subsets (or segments), and specify the operating
parameters for each segment individually. The Segment Block
has 5 outputs that can be used as inputs to other blocks. The
MFC supports a maximum of eight Segment Control Blocks.
The seven other Segment Control blocks can be placed in any
user configurable block. Refer to Tables 

4-4

 and 

4-5

.

Table 4-3.  Function Code 81 Block Outputs (System Constraints)

Block 

Number

Data

Type

Description

0
1
2

Boolean
Boolean
Boolean

Logic 0
Logic 1
0 or Real 0.0

3
4
5

Real
Real
Real

-100.0
-1.0
0.0

6
7
8

Real
Real
Real

1.0
100.0
-9.2E18 (maximum negative value)

9

10
11

Real

Boolean

Real

+9.2E18 (maximum positive value)
Start-up in progress flag (0 = no; 1 = yes)
Memory Display Value

12
13
14

Real
Real
Real

System free time in percent
Revision Level (hardware and firmware)
Reserved

Table 4-4.  Function Code 82 Specifications

Spec. 

No.

Tune*

Default 

Value

Data Type

Range

Min. Max.

Description

S1

No

1

Int(2)

1 to 2

Segment Attributes Tune Lock and Time Units

Tune Lock

0X = Tuning allowed
1X = Tuning not allowed

Time Units

X1 = Seconds
X2 = Minutes

S2

Yes

.250

Real(3)

Full

Target period (seconds/minutes)

S3

No

0

Int(2)

0 to 32,767 Segment priority (0 = lowest)

S4

No

1

Int(2)

0 to 32,767 Checkpoint period (number of cycles per 

checkpoint)

S5

No

0

Int(1)

0 to 1

PID reset mode

0 = normal
1 = external

S6

No

10.000

Real(3)

Full

PID maximum derivative gain

Содержание infi 90 IMMFC03

Страница 1: ... Process Control and Automation Solutions from Elsag Bailey Group E96 211 Multi Function Controller IMMFC03 ...

Страница 2: ...MENTS ÉLECTRONIQUES SONT SENSIBLES AUX PERTURBATIONS PAR FRÉQUENCE RADIO DES PRÉCAUTIONS DEVRONT ÊTRE PRISES LORS DE L UTILISATION DU MATÉ RIEL DE COMMUNICATION PORTATIF LA PRUDENCE EXIGE QUE LES PRÉCAUTIONS À PRENDRE DANS CE CAS SOIENT SIGNALÉES AUX ENDROITS VOULUS DANS VOTRE USINE PERTURBATIONS DU PROCÉDÉ L ENTRETIEN DOIT ÊTRE ASSURÉ PAR UNE PERSONNE QUALIFIÉE EN CONSIDÉRANT L ASPECT SÉCURITAIRE...

Страница 3: ...e Multi Function Controller Module IMMFC03 Related hardware such as I O slave modules termination units etc are also presented A complete list of hardware doc uments is listed in Section 1 under the Reference Documents heading Carefully read this document before putting the module into operation ...

Страница 4: ... 7 1 Original 8 1 Original 9 1 through 9 3 Original A 1 through A 9 Original B 1 through B 3 Original C 1 through C 3 Original D 1 through D 3 Original When an update is received insert the latest changed pages and dispose of the super seded pages NOTE On an update page the changed text or table is indicated by a vertical bar in the outer mar gin of the page adjacent to the changed area A changed ...

Страница 5: ...IC WARNINGS Disconnect power before installing dipshunts for slave modules on the MMU backplane slave expander bus Failure to do so could result in severe or fatal shock p 3 7 Strict adherence must be made with regard to the rules set forth in this document Follow all steps in the sequence given and at no time change configurations or remove the module before the LEDs instruct you to do so Failure...

Страница 6: ...ÉCIFIQUE Couper l alimentation avant d installer les dipshunts sur la plaque arriere du chassis de montage de modules MMU Toute negli gence a cet egard constitue un risque de choc pouvant entrainer des blessures graves voire moretlles p 3 7 Les procedures decrites dans ce document doivent etre suivies a la lettre Respecter l ordre des etapes et ne jamais apporter de changements a la configuration ...

Страница 7: ...ATIONS 1 8 SECTION 2 DESCRIPTION AND OPERATION 2 1 INTRODUCTION 2 1 MODULE DESCRIPTION 2 1 Microprocessor 2 1 Clock Timer 2 2 Memory 2 2 Slave Expander Bus 2 2 I O Section 2 2 Serial Channels 2 3 Module Bus 2 3 Redundancy Link 2 3 Station Link 2 3 DATA TRANSFER 2 3 SECURITY FUNCTIONS 2 4 HARDWARE MODULE SECURITY FUNCTIONS 2 4 Internal Software Security Functions 2 4 Control Software Security 2 5 I...

Страница 8: ...4 5 Function Code 82 Segment Control 4 6 Function Code 90 Extended Executive 4 8 BASIC LANGUAGE FUNCTION CODES 4 9 C Language Function Codes 4 9 SECTION 5 OPERATION 5 1 INTRODUCTION 5 1 INDICATORS AND CONTROLS 5 1 Status LEDs 5 1 CPU LEDs 5 2 Memory LEDs 5 2 Stop Pushbutton 5 2 Reset Pushbutton 5 3 OPERATING MODES 5 3 Execute Mode 5 3 Configure Mode 5 3 Error Mode 5 4 SECTION 6 TROUBLESHOOTING 6 1...

Страница 9: ...ATION A 1 INTRODUCTION A 1 SETUP A 1 OPERATION A 1 Backup Cycle A 4 Primary Cycle A 7 APPENDIX B NTMF01 TERMINATION UNIT CONFIGURATION B 1 INTRODUCTION B 1 CONFIGURING NTMF01 B 2 CABLE CONNECTIONS B 3 APPENDIX C NIMF01 TERMINATION MODULE CONFIGURATION C 1 INTRODUCTION C 1 CONFIGURING NIMF01 C 2 CABLE CONNECTIONS C 3 APPENDIX D NIMF02 TERMINATION MODULE CONFIGURATION D 1 INTRODUCTION D 1 CONFIGURIN...

Страница 10: ...s 6 5 6 6 Edge Connector P3 Pin Outs 6 5 7 1 Maintenance Schedule 7 1 8 1 Recommended Spare Parts List 8 1 List of Figures No Title Page 1 1 IMMFC03 Application Example 1 1 2 1 IMMFC03 Block Diagram 2 1 3 1 CPU Board Component Locations 3 2 3 2 Memory Board 3 4 5 1 Front Panel LED Indicators and Controls 5 1 9 1 IMMFC03 Firmware Revision Level Location 9 2 A 1 LED Legend A 3 A 2 Backup MFC Operati...

Страница 11: ...ent for the Network 90 NMFC03 Refer to Figure 1 1 for an application example INTENDED USER This manual is a guide for the system engineer or technician who configures operates or maintains the MFC in a system It explains the start up and service Follow the steps in this man ual closely to maintain and use the MFC properly Figure 1 1 IMMFC03 Application Example MFC MFC COMMUNICATION HIGHWAY OR PLAN...

Страница 12: ...e as the primary provides backup to the primary module In a redundant setup one module is the primary It performs computations runs control functions etc The other the backup module monitors tracks the primary The backup copies the primary control lers outputs and waits in a hot standby mode There is con stant communication between the primary and the backup module If the primary module should fai...

Страница 13: ...mmary of section content Introduction An overview of module capabilities electronic specifications glossary of unique terms and related documents Description and Operation Explains data transfer and security functions handled by the hardware and software Installation Preparatory steps switch settings etc to complete before put ting the module into service Additional termination informa tion is in ...

Страница 14: ...software related to the MFC Refer to them as needed Number Document I E96 702 I E96 703 I E96 710 Batch Language Compiler C Language Compiler User Defined FC Compiler I E96 906 6 I E96 916 16 I E93 900 20 MFC BASIC Programmer s Reference Manual MFC C Language Implementation Guide Function Code Application Manual I E96 117 I E96 303 I E96 304 Analog Control Station IISAC01 Analog Output Station IMA...

Страница 15: ... MCS Management Command System a CRT based operator monitor and control console also used in configuration MFT Machine Fault Timer reset by the processor during normal operation If there is an error the MFT times out and the module stops Module Bus Serial communication link between Multi Function Controller and other control modules e g Logic Master Module Controller etc OIS Operator Interface Sta...

Страница 16: ...o 20 mA 1 to 5 VDC and 4 digital outputs 24 VDC Digital Slave Input Module IMDSI02 L Supplies 16 contact inputs of 24 VDC 125 VDC or 120 VAC Pulse Counter IMDSM04 H Supplies 8 input channels that determine the count frequency or period of pulse or sine wave inputs Digital Slave IMDSM05 H Interfaces the MFC to up to 8 Digital Logic Stations Digital Slave Output Module IMDSO01 L IMDSO02 L IMDSO03 L ...

Страница 17: ...nt recorder In other cases only the NKMF02 cable for redundancy is required Microprocessor 68020 Memory 512 Kbytes of RAM 80 Kbytes of Battery Backed RAM non volatile 256 Kbytes of UVROM Communication Ports 2 RS 232 C Serial 2 RS 422 SAC DCS Link MFC to MFC redundancy Power Consumption 4 5 Amps nominal at 5 VDC 23 Watts 37 mA nominal at 15 VDC 0 6 Watts 18 mA nominal at 15 VDC 0 3 Watts Power Diss...

Страница 18: ...ion and control The processor s operat ing system instructions and the function code library reside in the read only memory ROM Since the processor is responsi ble for overall operation it communicates with all functional blocks The processor also does one other critical task It con stantly retriggers the Machine Fault Timer MFT circuit If the processor or software fails and the MFT is not reset t...

Страница 19: ... eight bit parallel bus that provides the communication path for I O data from slave modules It is capable of supporting 64 low power slaves both Network 90 and INFI 90 The bus uses Bailey designed protocol to ensure data integrity The bus bandwidth is 500 kilobytes per second I O Section The I O Section interface allows the processor to read the switches that tell it how to operate and set its ad...

Страница 20: ...terruption Station Link Station link controls the serial communication between the MFC and the panel stations It provides a 5 kilobaud serial channel for up to eight stations IISAC01 or NDCS03 This link connects to the termination unit or termination module for control stations via the NTMF01 or NIMF01 and the cable NKSE01 DATA TRANSFER The IMMFC03 uses two busses for communication purposes The mo...

Страница 21: ...al addresses in and above the MFC s allowable address range 16 megabytes If the processor sources an illegal address the address decoding hardware detects it and generates a bus error The front panel LEDs illu minate with the error message The third hardware check is the machine fault timer MFT The MFC processor periodically resets this timer If the timer is not reset it expires When this happens ...

Страница 22: ...rs are tagged by the MFC as bad quality Bad quality stays with the point no matter where it goes e g in the MFC on the module bus or the communication highway If you select to run the process using bad quality data the MFC uses the last valid value it had for the process point before the quality went bad The MFC then writes the bad qual ity information to its module status bytes and activates an O...

Страница 23: ...hen work ing with modules The kit is designed to connect a technician and the static dissipative work surface to the same ground point to pre vent damage to the modules by electrostatic discharge Special Handling The MFC uses MOS devices Follow the special handling proce dures below 1 Keep the module in the special anti static bag until you are ready to install it in the system Save the bag for fu...

Страница 24: ... logic 1 This applies to all MFC switches NOTES 1 When redundancy is used switches 1 through 7 on the redun dant MFC are set the same as the primary MFC 2 Record your settings in the USER SETTINGS column Switch U73 Baud Rate This switch is used to set the baud rates of the two RS 232 C ports of the MFC s Termination Unit NTMF01 or Termination Module NIMF01 The termination unit module provides seri...

Страница 25: ...he CONFIGURE mode and compacts the configuration 1 7 0 Initialize NVM erase configuration Leave switch OPEN insert module into MMU When front panel LEDs 1 2 and 4 are ON remove the module put the switch in the CLOSED position re insert the module The module is now ready to be configured NOTE This switch remains CLOSED for normal operation 1 8 0 Primary MFC 1 Redundant MFC Normal switch setting for...

Страница 26: ...er configurations NOTE These jumpers are set at the factory Do not change these settings This table is for information only Table 3 3 U75 Switch Settings Address Switch Position 1 2 3 4 5 Address Switch Position 1 2 3 4 5 Address Switch Position 1 2 3 4 5 2 0 0 0 1 0 12 0 1 1 0 0 22 1 0 1 1 0 3 0 0 0 1 1 13 0 1 1 0 1 23 1 0 1 1 1 4 0 0 1 0 0 14 0 1 1 1 0 24 1 1 0 0 0 5 0 0 1 0 1 15 0 1 1 1 1 25 1 ...

Страница 27: ...nt Loop To configure the MFC for use in the Plant Loop environment follow Steps 1 through 5 1 Set dipswitch U72 with poles 1 and 3 in the OFF open logic 1 position to perform a default MFC format operation All remaining poles must be in the ON closed logic 0 position NOTE This Step deletes the configuration and all files 2 Reset the module The Status LED turns red and LEDs 1 through 6 illuminate 3...

Страница 28: ...refer to Installing Modules 4 When the special operation is complete the Status LED turns red and LEDS 1 through 6 illuminate 5 Remove the module 6 Reset pole 1 to the 0 position Table 3 5 Switch U72 Special Operations Pole Value 1 128 2 64 3 32 4 16 5 8 6 4 7 2 8 1 Special Operation Description 1 0 0 0 0 0 0 0 0 Reserved Do not use If you use this setting your module may not operate properly 1 1 ...

Страница 29: ...e CPU Board NOT THE MEM BOARD 4 Slide the module into the slot push until the rear edge is firmly seated in the backplane connectors Lock the module in place by turning the two captive screws on faceplate 1 2 turn The module is in place when the notch on each screw is verti cal and the open end is pointing toward the center of the mod ule The green Status LED should illuminate If it does not refer...

Страница 30: ...onfiguration Tuning Terminal CTT Refer to the product instruction for your specific interface device for com plete configuration details FUNCTION BLOCKS The valid range of function block addresses is 0 to 9 998 How ever block addresses 0 through 29 are fixed meaning that you cannot assign function codes to them These blocks contain executive functions and system constants Blocks 30 through 9 998 a...

Страница 31: ...ons the highest priority The execution rates are listed in Table 4 1 4 Calculate the amount of NVM the configuration uses a Multiply 205 PID blocks by 36 bytes per block 7 380 bytes of NVM b Multiply 205 Square Root blocks by 12 bytes per block 2 460 bytes of NVM c Multiply 2 Segment Control blocks by 60 bytes per block 120 bytes of NVM d Add products 7 380 2 460 120 9 960 bytes of NVM There are 7...

Страница 32: ...f CPU time the configuration requires to run First calculate the maximum amount of CPU time Next calculate how much CPU time the low priority loops require a Multiply 100 PID blocks by 690 microseconds 0 069 seconds b Multiply 100 Square Root blocks by 190 microseconds 0 019 seconds c Add products 0 069 0 019 0 088 seconds of CPU time The result of this calculation gives the amount of CPU time tha...

Страница 33: ...e required for high priority function blocks to execute a Multiply 5 PID blocks by 690 microseconds 0 00345 seconds b Multiply 5 Square Root blocks by 190 microseconds 0 00095 seconds c Add products 0 00345 0 00095 0 00440 seconds The above sum represents CPU time used by one pass of the high priority loop d Multiply 20 times per second by 2 seconds 40 times in 2 seconds number of times the high p...

Страница 34: ...gh 14 Within these blocks are constant values that can be used as block inputs anywhere in the configuration Additionally this function is used to select the outputs of the front panel status LEDs Table 4 2 lists the specifications Table 4 3 lists the sys tem constants Table 4 2 Function Code 81 Specifications Spec No Tune Default Value Data Type Range Min Max Description S1 Yes 0 000 Int 2 0 1 Fr...

Страница 35: ...Boolean Boolean Boolean Logic 0 Logic 1 0 or Real 0 0 3 4 5 Real Real Real 100 0 1 0 0 0 6 7 8 Real Real Real 1 0 100 0 9 2E18 maximum negative value 9 10 11 Real Boolean Real 9 2E18 maximum positive value Start up in progress flag 0 no 1 yes Memory Display Value 12 13 14 Real Real Real System free time in percent Revision Level hardware and firmware Reserved Table 4 4 Function Code 82 Specificati...

Страница 36: ...n Table 4 5 Function Code 82 Block Outputs Block Number Description N Elapsed time of the previous execution cycle in S1 units including any segment idle time If the time required to run the block is less than the requested cycle time the remainder is idle time spent waiting before starting the next cycle Any idle time is available for lower priority segments This output is used to verify that the...

Страница 37: ...xt highest priority segment must be increased until no overrun occurs N 4 Cycle time overrun in units specified by S1 If cycle time exceeds that set by S14 the overrun is output from this block This output enables you to program logic to take specific action based on a given cycle time alarm limit being exceeded Table 4 5 Function Code 82 Block Outputs continued Block Number Description Table 4 6 ...

Страница 38: ...uration Refer to the Function Code Application Manual for specifications Complete instructions for programming in BASIC or C can be found in the programmer s reference manuals Table 4 7 Function Code 90 Block Outputs Block Number Data Type Description 20 21 22 Real Real Real Time of day hours Time of day minutes Time of day seconds 23 Boolean Time date synchronization flag 0 time date invalid 1 va...

Страница 39: ... two Memory Status LEDs and Stop and Reset pushbuttons Status LEDs The Status LED is a red green LED that indicates MFC operat ing condition It has four possible states Off Indicates that the MFC is not powered Solid Green Indicates that the MFC is in the Execute mode Figure 5 1 Front Panel LED Indicators and Controls CPU LEDS LSB MSB STATUS LED MEMORY LEDS RESET PUSHBUTTON STOP PUSHBUTTON T00010A...

Страница 40: ...ion NOTE When contacting Bailey personnel about problems with your IMMFC03 it is important to indicate the error codes shown on the CPU LEDs Memory LEDs There are two Memory LEDs MEM LED 2 illuminates only when single bit errors are being corrected Both LEDs illumi nate when two bit errors three bit errors or complete memory failure occur Stop Pushbutton The Stop pushbutton performs the following ...

Страница 41: ...ed adjusted but configurations cannot be modified The status LED is solid green indicating normal operation However in certain nonfatal error conditions the LED flashes green but the MFC continues to operate Configure Mode The Configure Mode is used to enter or modify the configura tion that makes up the user s control strategy In this mode function blocks can be added modified or deleted by using...

Страница 42: ...when an error occurs Stops execution the Status LED turns red The slave outputs hold their present value or go to user selected default state OR Continues to execute but marks the I O data of the failed slave as Bad Quality When the MFC s status is read by the user s interface device the slave failure is detected When the operator inquires he is advised of a slave failure and can take corrective a...

Страница 43: ...figurations on NTCS02 T U Also check specifications of applicable function codes 0 0 0 0 0 0 1 1 03 Slave status error wrong type or not responding Check switch settings on slave modules Check dipshunt configuration on NIMF01 Also check specifications of applicable function codes 0 0 0 0 0 1 0 1 05 Configuration error undefined block Check configuration Add appropriate function codes blocks 0 0 0 ...

Страница 44: ... C configuration check module s file directory for program files 0 0 1 0 0 0 1 1 23 User write violation Program attempted to write outside the allow able user address space Check the C program for writes to null pointers etc 0 0 1 0 0 1 0 0 24 Stack overflow detected C program wrote past the end of the stack Check the C program for unbounded stack growth 0 0 1 0 1 1 1 1 2F BASIC error Check BASIC...

Страница 45: ...ed information on MFC error conditions Any of the INFI 90 operator interface devices can be used to access these words Refer to the product instruction for your specific interface device for details Table 6 2 Status Bytes Byte Bit 7 6 5 4 3 2 1 1 ES MODE TYPE 2 FTX BAC RIO LIO N A NVI CFG N A 3 PCU MEM NEF N A N A N A N A N A 4 LIE LRE LRE LTE LTE N A N A N A 5 N A N A N A N A N A N A N A N A ...

Страница 46: ...05 06 08 0F 10 4 01 02 03 FF 1 1 1 1 1 5 2 2 2 2 2 NVM Error Write Failure Checksum Failure Bad Data Reset During Write Analog Input Reference Error 1 2 Block number of Control Interface Slave block Missing Slave Module or Slave Expander Board 1 2 Block number of slave module or Digital Station Configuration Error undefined block 1 2 Block making reference Configuration Error input data type is in...

Страница 47: ...rue Data Bit D4 low true Data Bit D6 low true Sync N C Table 6 6 Edge Connector P3 Pin Outs Pin No Signal Pin No Signal 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 SAC DCS Link Redundancy Link Transmit Data Redundancy Link Receive Data Terminal Port Transmit Data Terminal Port Request to Send Terminal Port Data Carrier Detect Printer Port Transmit Data Printer Port Request to Send Printer Port Data Carrie...

Страница 48: ... Perform the tasks in Table 7 1 at the specified intervals Table 7 1 Maintenance Schedule Task Interval Clean and tighten all power and grounding connections Every 6 months or during plant shutdown whichever occurs first Use a static safe vacuum cleaner to remove dust from Modules Module Mounting Unit Fan Assembly Power Entry Panel Every 6 months or during plant shutdown whichever occurs first ...

Страница 49: ...removed 4 Hold the module by the faceplate and slide it into the slot push until the rear edges are firmly seated in the backplane connectors 5 Turn the two concentric screws one half turn clockwise to lock the module into the Module Mounting Unit The module is locked when the notches on the front of the knobs are pointing toward the middle of the module Table 8 1 Recommended Spare Parts List Desc...

Страница 50: ... a commercial description provided must be ordered from your nearest Bailey sales service office Recommended spare parts lists including prices on standard assemblies are also avail able through your nearest Bailey sales service office When ordering a Multi Function Controller Module as a replacement for your system in a redundant configuration your Bailey representative needs to know the revision...

Страница 51: ...n example of Block 13 output is shown 3 0 0 0 Firmware Revision Level 00 A_0 Hardware Revision Level Module Nomenclature 3 IMMFC03 Call your Bailey Sales Representative with this information tell him you want the latest version TRAINING Bailey Controls has a modern training center equipped to pro vide service and repair instruction which is available for in plant training of customer personnel Spe...

Страница 52: ...dditional copies of this publication can be obtained through your nearest Bailey sales service office If any questions arise on the ordering procedure please con tact your Bailey representative Our Global Technical Support Department is also available to answer your technical ques tions at 1 800 4 BAILEY ...

Страница 53: ...th the new configuration while the original primary MFC takes the backup role During start up of the new configuration in the backup MFC the present values of all process outputs in the primary MFC are used This feature permits bumpless transfer of control to the new configuration SETUP On line configuration of redundant MFCs requires two consec utive module bus addresses to be reserved In normal ...

Страница 54: ... interface device determines how module status is acquired For example using an operator interface station OIS the status is polled by selecting the module in the PCU status display selected from the system status display With an EWS using CAD TEXT software the problem report option must be selected Note that this option does not continuously poll for module status The EWS operator may have to pol...

Страница 55: ... backup and primary cycles For clarity the term backup MFC will always refer to the origi nal backup MFC and the term primary MFC will always refer to the original primary MFC When the roles are reversed for either unit their status will be carefully noted Legend Primary Backup Module Address n n 1 Second Module Status Byte Bit 7 6 5 4 3 2 1 0 0 1 x x 0 x 0 x Bit 7 6 5 4 3 2 1 0 1 0 x x 1 x 0 x LE...

Страница 56: ... 1 00xx0x0x 10xx0x0x z z z 1 Save a copy of the old configuration This enables it to be easily restored if necessary Figure A 2 Backup MFC Operation Cycle CHECKPOINT DATA IS COMPLETE 4 BACKUP EXT 3 BACKUP EXT 2 BACKUP CFG 1 BACKUP EXT 2A BACKUP ERR 9 PRIMARY EXT 8 PRIMARY EXT 7 BACKUP EXT 6 BACKUP EXT 5 BACKUP EXT T00040A LEGEND EXT EXECUTE MODE CFG CONFIGURATION MODE ERR ERROR MODE BUSCLK LOSS OF...

Страница 57: ...rules are strictly enforced by the module 1 Blocks can only be added in the block space at the end of a segment 2 A block existing in the primary MFC cannot be deleted 3 A specification change cannot be made to a block already exist ing in the primary MFC if that change effects the module utilization factor change memory requirements 4 Do not attempt to change segment control block priority 5 Comp...

Страница 58: ...s detected in the old configuration refer to Step 9 However the primary MFC still indicates that no backup is available when the con figuration is different Additional configuration changes can be made by entering CONFIGURE mode Step 2 If no changes have been made at this point a stop and reset returns the backup MFC to Step 1 Primary Backup n n 1 01xx0x0x 00xx1x0x z z 6 A stop and reset at this s...

Страница 59: ...rimary MFC currently acting as the hot backup tells it to get a copy of the new configuration The pri mary MFC must be stopped and reset at this point in order for the cycle to complete Primary Backup n n 1 10xx0x0x 00xx0x0x z z z 11 After the backup MFC copies the new configuration into the primary MFC this cycle is complete The backup MFC is now serving as the primary MFC while the primary handl...

Страница 60: ... backup can take control using the old configuration and block output information returns to Step 1 Primary Backup n 1 n 00xx0x0x 00xx1x0x 5 5 4 Stopping and resetting the primary MFC currently acting as the hot backup tells it to get a copy of the new configuration Step 9 of the backup cycle Primary Backup n 1 n 10xx0x0x 00xx0x0x z z z 5 When the new configuration has been copied the backup MFC h...

Страница 61: ... Cycle 1 PRIMARY EXT 2 PRIMARY EXT 6 BACKUP EXT SHUTDOWN REQUESTED 3 HOT BACKUP EXT 4 BACKUP EXT 5 BACKUP EXT COPY THE PRIMARY S CONFIGURATION STEP ROLE MODE LEGEND EXT EXECUTE MODE BUSCLK LOSS OF BUS CLOCK TP50245A CHECKPOINT DATA IS COMPLETE BUSCLK BUSCLK SHUTDOWN COMPLETE RESET ...

Страница 62: ...he termination unit configure the outputs Figure B 1 shows the input connectors dipshunts and output ports on the termination unit Figure B 1 NTMF01 Termination Unit T00012A DTE DCE DTE DCE P1 P3 E3 E2 P2 P5 P6 P1 CONNECTOR P3 CONNECTOR XU1 DIPSHUNT XU4 DIPSHUNT TERMINAL PORT PRINTER PORT XU1 DIPSHUNT XU3 DIPSHUNT 24 VDC COMMON STATION COMMUNICATION P2 CONNECTOR CR23 MCA A ACTIVE CR22 MCA B ACTIVE...

Страница 63: ...t Configuration Multi Function Controller Module IMMFC03 04 05 NKTU01 Sequential Events Recorder IBM PC COMPAQ Compatible Computers Terminals VT1XX ADM3 VISUAL 50 WYSE WY50 TELEVIDEO IBM Registered trademark of International Business Machines Corporation COMPAQ Registered trademark of COMPAQ Computer Corporation Figure B 2 NTMF01 Dipshunt Configurations DIPSHUNTS XU1 XU2 NOT USED XU3 1 2 3 4 5 6 8...

Страница 64: ...m the NTMF01 to the MFC and the output devices The output devices are the monitor printer and Control Station Termination Unit NTCS02 Figure B 3 NTMF01 Cable Connections IMMFC03 04 05 P3 IMMFC03 04 05 P3 PRINTER T00014A TERMINAL P1 P3 PRINTER PORT TERMINAL PORT P2 P1 P3 P5 P4 P2 NTCS02 NTMF01 NKTU01 NKTU01 RS 232 C RS 232 C NKSE01 ...

Страница 65: ...puts For redundant systems the MFC module uses both an NIMF01 and NIMF02 to connect with output devices refer to Appendix D Dipshunts on the termination module configure the outputs Figure C 1 shows the dipshunts input connectors and output ports on the termination module Figure C 1 NIMF01 Termination Module 3 5 2 4 1 TERMINAL 1 J3 SOCKET T00015A TERMINAL 5 LED TERMINAL PORT PRINTER PORT DIPSHUNTS...

Страница 66: ...ype Dipshunt Configuration Multi Function Controller Module IMMFC03 04 05 NKTU02 or NKTM01 Sequential Events Recorder IBM PC COMPAQ Compatible Computers Terminals VT1XX ADM3 VISUAL 50 WYSE WY50 TELEVIDEO IBM Registered trademark of International Business Machines Corporation COMPAQ Registered trademark of COMPAQ Computer Corporation Figure C 2 NIMF01 Dipshunt Configurations DIPSHUNTS XU1 XU2 NOT U...

Страница 67: ...nd the output devices The output devices are the monitor printer and control station termination module NICS01 Figure C 3 NIMF01 Terminal Assignments TERMINAL NUMBER SERIAL LINK 1 GND 2 COM 3 24 VDC 4 5 T00016A Figure C 4 NIMF01 Cable Connections T00017A P3 P1 NKTM01 OR NKTU02 TERMINAL PORT TB TB 5 22 4 21 PRINTER PORT NIMF01 NICS01 SERIAL LINK IMMFC03 04 05 ...

Страница 68: ...ant systems the primary MFC module uses an NIMF01 and the redundant MFC uses the NIMF02 to connect output devices Dipshunts on each termination module configure the outputs The green LED lights on the active termination module Figure D 1 shows the dipshunts input connectors and output ports on the termination module Figure D 1 NIMF02 Termination Module 3 2 1 TERMINAL 1 J3 SOCKET T00018A LED TERMIN...

Страница 69: ...es To Connecting Cable Application Signal Type Dipshunt Configuration Multi Function Controller Module IMMFC03 04 05 NKTU02 or NKTM01 Sequential Events Recorder IBM PC COMPAQ Compatible Computers Terminals VT1XX ADM3 VISUAL 50 WYSE WY50 TELEVIDEO IBM Registered trademark of International Business Machines Corporation COMPAQ Registered trademark of COMPAQ Computer Corporation Figure D 2 NIMF02 Dips...

Страница 70: ...witching between the two termination modules NIMF02 con nects to an NICS01 through a twisted pair between the serial termination blocks on each module This provides a communi cation link between a multi function controller and a control station Figure D 3 NIMF02 Terminal Assignments TERMINAL NUMBER 1 GND 2 COM 3 24 VDC T00019A Figure D 4 NIMF02 Cable Connections T00020A P3 P3 P1 P1 NKTM01 OR NKTU0...

Страница 71: ...8756 ASIA PACIFIC 152 Beach Road Gateway East 20 04 Singapore 189721 Telephone 65 391 0800 Telefax 65 292 9011 EUROPE AFRICA MIDDLE EAST Via Puccini 2 16154 Genoa Italy Telephone 39 10 6582 943 Telefax 39 10 6582 941 GERMANY Graefstrasse 97 D 60487 Frankfurt Main Germany Telephone 49 69 799 0 Telefax 49 69 799 2406 Form I E96 211A Litho in U S A 1190 Copyright 1990 by Elsag Bailey Process Automati...

Отзывы: