INSTALLATION
INSERTING THE MFC IN THE MODULE MOUNTING UNIT
I-E96-211A
3 - 7
7. Reset poles 2 through 6 per Table
.
8. Insert the module in its slot. It will enter its normal operat-
ing mode.
INSERTING THE MFC IN THE MODULE MOUNTING UNIT
After performing the necessary switch configurations, the
module is ready to be installed in the module mounting unit
(MMU).
To insert the MFC:
1. Verify the slot assignment of the module. Note that the
MFC occupies two slots (one for the CPU board; the other for
the MEM board).
2. Install the supplied dipshunt between the slots on the
MMU backplane.
3. Connect the cable from the NTMF01 Termination Unit (or
NIMF01 Termination Module) to the P3 card edge connector of
the CPU Board NOT THE MEM BOARD.
4. Slide the module into the slot; push until the rear edge is
firmly seated in the backplane connectors. Lock the module in
place by turning the two captive screws on faceplate 1/2 turn.
The module is in place when the notch on each screw is verti-
cal and the open end is pointing toward the center of the mod-
ule.
The green Status LED should illuminate. If it does not, refer to
.
The module is now ready to be configured. Follow the steps in
.
WARNING
Disconnect power before installing dipshunts for slave mod-
ules on the MMU backplane (slave expander bus). Failure to do
so could result in severe or fatal shock.
AVERTISSEMENT
Couper l'alimentation avant d'installer les dipshunts sur la
plaque arriere du chassis de montage de modules (MMU).
Toute negligence a cet egard constitue un risque de choc pou-
vant entrainer des blessures graves, voire moretlles.