![background image](http://html1.mh-extra.com/html/bailey/infi-90-imdso04/infi-90-imdso04_instruction_3479388014.webp)
INTRODUCTION
SPECIFICATIONS
I-E96-313A
1 - 5
SPECIFICATIONS
Power Requirements
Voltage
+5 VDC (
±
5%)
Current Consumption
135 mA (typical)
200 mA (maximum)
Dissipation (logic only)
750 mW (typical)
1.2 W (maximum)
Outputs
Load Voltage
24 VDC
Load Current (maximum)
250 mA
Off Leakage Current (maximum)
10
µ
A @ 70
o
C (158
o
F)
On Voltage Drop (maximum)
2.4 V @ 70
o
C (158
o
F)
Current Consumption
150 mA (typical), 250 mA (maximum)
Isolation
300 V rms between output and logic circuitry and output to output. CSA approved for 300 V isolation.
Surge Withstanding Capability
Meets ANSI/IEEE C37.90A-1974 "Guide for Surge Withstanding Capability Test".
Mounting
Occupies one slot in a standard Infi 90 module mounting unit.
Environmental
Ambient Temperature
0
o
to 70
o
C (32
o
to 158
o
F)
Relative Humidity
0 to 95% up to 55
o
C (131
o
F) (non-condensing)
0 to 45% at 70
o
C (158
o
F) (non-condensing)
Atmospheric Pressure
Sea level to 3 km (1.86 miles)
Air Quality
Non-corrosive
Certification
CSA certified as process control equipment in an ordinary (non-hazardous) location .