INTRODUCTION
SPECIFICATIONS
WBPEEUI240752A0
1 - 7
Isolation
(IEC 1010-1, IEC 255, IEC 60)
Channel to channel and channel to
logic
Electromagnetic compatibility
Conducted transients
Electrostatic discharge
(IEC 1000-4-2, EN 61000-4-2)
Contact: ±6 kV
Air: ±8 kV
Magnetic and electromag-
netic fields
Power frequency magnetic field
(IEC 1000-4-8, EN 61000-4-8)
Continuous: 30 A/m (rms)
Short duration: 300 A/m (rms)
Pulse magnetic field
(IEC 1000-4-9, EN 61000-4-9)
Peak value: 300 A/m
Damped oscillatory magnetic
field, 0.1 MHz and 1 MHz
(IEC 1000-4-10, EN 61000-4-10)
Peak value: 30 A/m
Radiated radio-frequency elec-
tromagnetic field, 80 MHz to
1GHz (ENV 50140)
Unmodulated rms: 10 V/m
Amplitude modulated: 80% AM (1 kHz)
Radiated radio-frequency field,
900 ±5 MHz
(ENV 50204)
Unmodulated rms: 10 V/m
Pulse modulated: Duty cycle 50%
Rep. cycle 200 Hz
Table 1-5. Specifications
Property
Characteristic/Value
Test
Common Mode
Normal
Mode
IMDSI12/15
Insulation resistance
(100/500 VDC)
100 M
Ω
N/A
Dielectric VAC (45 - 65 Hz) or
VDC
1.4 kV rms/1min. or
1.95 kV DC/1min.
N/A
Impulse voltage (1.2/50 µS)
±2.55 kVp
±1 kVp
IMDSI13/14
Insulation resistance
(100/500 VDC)
100 M
Ω
N/A
Dielectric VAC (45 - 65 Hz) or
VDC
1 kV rms/1min. or
1.5 kV DC/1min.
N/A
Impulse voltage (1.2/50 µS)
±2 kVp
±1 kVp
Test
Common Mode
Normal
Mode
Voltage/current surge
(1.2/50 µS to 8/20 µS )
(IEC 1000-4-5, EN 61000-4-5)
±2 kVp
±1 kVp
Fast transient bursts
(IEC 1000-4-4, EN 61000-4-4)
±2 kVp
N/A
Damped oscillatory wave,
0.1 MHz and 1 MHz
(IEC 1000-4-12, EN 61000-4-12)
±2 kVp
±1 kVp
Ring wave
(IEC 1000-4-12, EN 61000-4-12)
±2 kVp
±1 kVp