INSTALLATION
SETUP/PHYSICAL INSTALLATION
WBPEEUI240752A0
3 - 5
2. Repeat step 1 until the jumpers are set for group A and
group B inputs.
Table 3-2. Working Voltage Settings
(IMDSI12 only)
Input
Jumper
+24 VDC +48 VDC
125 VDC/
120 VAC
A1
J1
2-3
1-2
3-4
A2
J3
2-3
1-2
3-4
A3
J5
2-3
1-2
3-4
A4
J7
2-3
1-2
3-4
A5
J9
2-3
1-2
3-4
A6
J11
2-3
1-2
3-4
A7
J13
2-3
1-2
3-4
A8
J15
2-3
1-2
2-3
B1
J17
2-3
1-2
3-4
B2
J19
2-3
1-2
3-4
B3
J21
2-3
1-2
3-4
B4
J23
2-3
1-2
3-4
B5
J25
2-3
1-2
3-4
B6
J27
2-3
1-2
3-4
B7
J29
2-3
1-2
3-4
B8
J31
2-3
1-2
3-4
Table 3-3. DC/AC Mode Settings
(IMDSI12 and IMDSI15)
Input
Jumper
AC Mode
DC Mode
A1
J2
1-2
3-4
A2
J4
1-2
3-4
A3
J6
1-2
3-4
A4
J8
1-2
3-4
A5
J10
1-2
3-4
A6
J12
1-2
3-4
A7
J14
1-2
3-4
A8
J16
1-2
3-4
B1
J18
1-2
3-4
B2
J20
1-2
3-4
B3
J22
1-2
3-4
B4
J24
1-2
3-4
B5
J26
1-2
3-4
B6
J28
1-2
3-4
B7
J30
1-2
3-4
B8
J32
1-2
3-4