INTRODUCTION
SPECIFICATIONS
1 - 6
WBPEEUI240752A0
®
SPECIFICATIONS
contains the specifications for the IMDSI1
digital
input module.
NKTU11
Cable, termination unit (non PVC)
NKTU12
Cable, termination module (non PVC)
NTDI01
Termination unit, digital input
Table 1-4. Related Hardware
(continued)
Nomenclature
Description
Table 1-5. Specifications
Property
Characteristic/Value
Power consumption
95 mA at 5 VDC (typical), 115 mA maximum
Overvoltage category on inputs
II, per IEC 1010-1
Digital inputs
16 channels
Communication interface
Passive contact input interface read by the MFP or logic master mod-
ule (LMM) via the I/O expander bus
Mounting
Occupies one slot in a standard INFI 90 OPEN module mounting unit
(IEMMU)
Environmental
Ambient temperature
(per IEC 68-2-1, 2,14)
Temperature rating within the cabinet or enclosure applies. INFI 90
OPEN internal cabinet rating: 0° to 70° C (32° to 158° F)
Relative humidity
(per IEC 68-2-3)
5% to 95% up to 55° C (131° F), noncondensing
5% to 45% at 70° C (158° F), noncondensing
Pollution degree: 1 (no condensation)
Atmospheric pressure
Sea level to 3 Km (1.86 miles)
Air quality (per ISA S71.04,
Class LA, LB, LC - level 1)
Noncorrosive
Voltage (
±
10%)
Current
Turn-on voltage (min)
Tun-off voltage (max)
Maximum input current at
minimum turn-on
Off-leakage current (max)
DC response time
(debounce filter)
IMDSI12
IMDSI13
IMDSI14
IMDSI15
24 VDC
48 VDC
125 VDC
120 VAC
5.5 mA
4.7 mA
4.5 mA
4.8 mA
16.8 VDC
20.1 VDC
69.3 VDC
54 VAC
13 VDC
29 VDC
58 VDC
48 VAC
4 mA at
14.7 VDC
4 mA at 32 VDC 4 mA at
68.4 VDC
3 mA at
53.8 VAC
7 µA (at V
in
≤
12 VDC)
10 µA (at V
in
≤
12 VDC)
10 µA (at V
in
≤
60 VDC)
10 µA (at V
in
≤
60 VAC)
17 ms (fixed)