INTRODUCTION
I-E96-207A
6 - 1
SECTION 6 - TROUBLESHOOTING
INTRODUCTION
This section explains the error indications and corrective
actions for the Controller Module (IMCOM03/04).
ERROR INDICATIONS AND CORRECTIVE ACTION
Obtain the status of the COM through an INFI 90 operator
interface (e.g. Operator Interface Station, Engineering Work
Station, Configuration and Tuning Terminal) or the front panel
module status LED indicator.
Status LED
The front panel status LED has three states to indicate normal
operation and error conditions. Table
lists the symptom
and recovery procedures for execute errors.
Controller Module Errors
The controller module performs its own status checks. An error
will appear in the report function of an operator interface. Refer
to the product instruction for the operator interface you are
using for an explanation of these reports.
NOTE: Refer to the product instruction for your configuration device
when referring to this table.
Table 6-1. Status LED Indications and Corrective Actions
Symptom
Problem
User Action
Flashing green LED when COM is
in the EXECUTE mode.
An error (non-fatal one that does
not immediately affect the execu-
tion) exists.
Use a non-conductive pointed
instrument to press the RESET
switch through the COM faceplate.
The COM is not in ERROR mode.
Use the CTM to obtain the status
word for the type of error.
Put the COM in CONFIGURE
1
mode to correct the error.
Solid red LED when the COM is in
the EXECUTE mode.
A fatal error (one that immediately
affects the execution) exists.
Remove COM and replace with a
known good one. Follow the
instructions in
to con-
figure the replacement).
NOTE:
If the status word indicates an NVRAM error, PUTTING THE COM IN THE CONFIGURE MODE WILL ERASE ANY EXISTING
CONFIGURATION. You will need to re-configure the mode using your configuration chart. Or you can remove the COM and insert replace-
ment configured COM.