CONFIGURATION
CONFIGURATION
4 - 2
I-E96-207A
®
CONFIGURATION
WARNING
The module digital outputs are de-energized (off) during
start-up, during operator selected RESET, configure mode and
for certain failure conditions. Configure the control strategy to
prevent personal injury, equipment damage or damage to the
product in case digital outputs de-energize.
Analog outputs always hold last value when the module is put
into configure mode and go to user-selected values during
start-up, during operator selected RESET, and for certain fail-
ure conditions. These values must be selected on the default
switch by the end user to prevent personal injury, equipment
damage or damage to the product.
AVERTISEMENT
French translation to be supplied later.
WARNING
Independent of the user-selected default values, it is possible
for the analog or digital outputs to fail in the on state. This is
characteristic of solid-state circuits. A solid state-circuit failure
in the on state could cause personal injury or significant equip-
ment damage in some applications. Additional interlocks such
as overstroke and overlevel limit switches or pressure and
temperature limiting valves must be put in the system where
operation or maintenance personnel may be working or where
there may be serious equipment damage.
The module analog outputs change to user-selected values
during start-up, during operator selected RESET or STOP, and
for certain failure conditions. These values must be selected
by the end user to prevent personal injury, equipment damage
or damage to the product.
AVERTISEMENT
French translation to be supplied later.