INSTALLATION
TERMINATION MODULE CONFIGURATION
3 - 8
I-E96-207A
®
will retain data in the event of a power failure. Use the follow-
ing sequence for a new unconfigured module.
1. Remove module from the module mounting unit (MMU)
rack.
2. Verify that position 1 of switch S4 is CLOSED (Refer to Fig-
ure
for switch locations).
3. Set position 2 of S4 to OPEN position.
4. Re-insert module into MMU rack.
5. Allow module to initialize (the LED starts blinking green).
Leave in the rack for approximately 60 seconds.
6. Remove module from MMU rack.
7. Set position 2 of S4 to CLOSED position.
8. Reinsert the module to MMU rack.
9. Use the configuration and tuning module or other operator
interface device to enter configuration data. Refer to
for configuration information.
TERMINATION MODULE CONFIGURATION
A termination module (TM) connects the field device wiring to
the INFI 90 system. The terminal blocks (connection points) are
located on the TM.
You must configure the TM to accept the field inputs that are
sent to the COM, and to output the COM signals that are sent
to the process field device. Refer to the appendices to deter-
mine the configuration for your application.
PHYSICAL INSTALLATION
NOTE: The installation section provides instructions pertaining to
the physical installation of the COM only. For complete cable and
TU/TM information, refer to
The Controller Module (IMCOM03/04) inserts into a standard
INFI 90 module mounting unit (MMU) and occupies one slot.
To install:
1. Verify the slot assignment of the module.
2. Connect the hooded end of the termination cable from the
TU/TM to the MMU backplane. To do this, insert the connector