INSTALLATION
INSTALLING THE TERMINATION UNIT/MODULE AND FIELD WIRING
3 - 2
I-E96-314A
®
4. Use the original packing material and container to store the
module.
5. Store the module in an environment of good air quality,
and free from temperature and moisture extremes.
INSTALLING THE TERMINATION UNIT/MODULE AND FIELD WIRING
For information about installing process wiring and the digital
input termination unit (TDI) or the digital input termination
module (IDI), refer to the TDI or IDI termination instruction. To
install the termination unit or module and field wiring:
Termination Unit Installation
1. Install the magnetic pickup according to the manufac-
turer's directions.
2. Configure the dipshunt on the termination unit. (Refer to
the TDI instruction I-E96-424 for dipshunt settings.)
3. Install the termination unit on the termination mounting
panel and secure into place.
4. Connect the wiring from the magnetic pickup to the termi-
nation unit.
5. Connect the hooded end of the NKTU01 cable to the rear of
the Module Mounting Unit (MMU) slot for the FCS. Connect the
other end of the cable to the P1 connector on the termination
unit.
Termination Module Installation
1. Install the magnetic pickup according to the manufac-
turer's directions.
2. Configure the jumpers on the termination module. (Refer to
the IDI instruction I-E96-410 for jumper settings.)
3. Connect one end of NKTM01 or NKTU02 cable to the rear of
the Termination Mounting Unit (TMU) slot for the termination
module. Connect the other end of the cable to the rear of the
MMU slot for the FCS.
4. Insert the termination module in assigned slot of the TMU
leaving the terminals for process wiring exposed.
5. Connect the wiring from the magnetic pickup to the termi-
nation module.
6. Push the module into the TMU until it seats in the termina-
tion module connector.