INSTALLATION
SETTING THE SLAVE EXPANDER BUS ADDRESS
I-E96-314A
3 - 3
SETTING THE SLAVE EXPANDER BUS ADDRESS
The FCS must have its slave expander bus address set to be
able to communicate with the processor module. The user can
select an address for the FCS from 0 to 63. The address is set
with switch SW1, an 8-pole dipswitch. Poles 1 and 2
must be
set to 0 (closed or on). Pole 3 has a binary value of 32. Pole 8 is
the least significant bit with a binary value of 1 (open or off).
See Figure
for the dipswitch location. Refer to Table
for
examples of address settings. Record your address in the user
setting column.
Figure 3-1. Switch SW1 - Slave Expander Bus Address
P1
P3
P2
TP50149A
SW1
OPEN
7
6
2 3 4 5
1
8
1
2
3
4
5
8
6
7
OPEN
MSB
LSB
EDGE
CONNECTORS
Table 3-1. Slave Expander Bus Address Examples
Example Settings
Address
Example
Switch Position
1
2
3
4
5
6
7
8
Binary Value
128
64
32
16
8
4
2
1
15
0
0
0
0
1
1
1
1
32
0
0
1
0
0
0
0
0
63
0
0
1
1
1
1
1
1
User Settings
User
Assigned
Address
Switch Position
1
2
3
4
5
6
7
8
Binary Value
128
64
32
16
8
4
2
1