INSTALLATION
WIRING CONNECTIONS AND CABLING
3 - 2
I-E96-216A
®
2. Lock the module in place by turning the two captive screws
on faceplate one-half turn. The module is in place when the
notch on each screw is vertical and the open end is pointing
toward the center of the module.
3. Connect the CTT cable to the connector on the front of the
CPM. Check the cable to see that it is seated.
4. If the CTT does not power up refer to
.
NOTE: A CPM module can be removed or installed without power-
ing down the system.
WIRING CONNECTIONS AND CABLING
The CPM has one card edge connector (P1) to supply logic
power and provide digital communications. It has a five pin
connector on the faceplate to connect the CTT.
Wiring
Installing the module in the MMU connects the CPM to the +5
VDC logic power at P1. The +5 VDC is necessary to drive the
CTT circuitry. It also connects P1 to the module bus/control-
way for communication with the master modules. The P1 con-
nection requires no additional wiring or cabling.
Cable Connections
The CPM connects to the CTT with the five foot flexible cord
permanently attached to the CTT (see Figure
Figure 3-1. IMCPM01 Cable Connections and Termination
CTT
TP35833A
P1
IMCPM01
MODULE
BUS