INSTALLATION
OIC INSTALLATION
3 - 20
I-E96-192-5A
®
IIOIC424 Panel Mount Installation and Setup
Before the OIC console is set into place, insure that the support-
ing panel is strong enough to support the monitor. Figure
shows the monitor and keyboard interface assembly cut-out
dimensions. Use the following procedure to mount the panel:
1. The bezel must be removed before mounting the unit to the
panel. Remove the two cover mounting screws and remove top
cover.
2. Disconnect the brightness/contrast cable at the CRT and
degauss switch at the power entry panel. Disconnect AC power
cord and CRT and any external cables from the power entry
panel, if necessary. Remove the power entry panel.
3. Remove the four CRT mounting screws and move the CRT
forward to expose bezel mounting screws.
4. Remove the four bezel mounting screws and remove the
bezel.
5. Reverse the procedures when the unit is installed in the
panel. Torque all fasteners to 39.8 Nm (40 in.-lbs.).
The back of the power entry panel has a connector for AC input,
alarm relay outputs (24 VDC) and the monitor cables. The key-
board interface assembly is mounted on a separate panel. It has
the connectors for operator devices such as keyboard, trackball
or mouse, and a tune/off/configuration keyswitch. The alarm
relay outputs are for alarm annunciation only.
Figure 3-14. IIOIC424 Panel Mount Dimensions
NOTES:
1. LOCATE KEYBOARD
INTERFACE PANEL W ITHIN
1.83 M (6 FT) OF MONITOR.
2. CUTOUT TOLERANCES
ARE ±0.25 MM (±0.01 IN.)
UNLESS OTHERW ISE
SPECIFIED.
CUTOUT FOR
KEYBOARD
INTERFACE PANEL
CUTOUT FOR 19-IN. PANEL MOUNT
KEYBOARD MOUNTING HOLE PATTERN
209.6
8.25
6.4
0.25
95.3
3.75
8.7
0.38
228.6
9.00
374.7
14.75
135.9
5.35
368.3
14.50
114.3
4.50
457.2
18.00
101.6
4.00
MINIMUM SIDE CLEARANCE
(BOTH SIDES)
472.9
18.62
94.0
3.70
152.4
6.0
76.2
3.00
6.4 4 HOLES
0.250
4.8 4 HOLES
0.19
TP35327B
.
DIMENSIONS
MILLIMETERS
INCHES
7.9 6 HOLES
0.312
196.9
7.75
MINIMUM TOP
CLEARANCE