INSTALLATION
OIC INSTALLATION
I-E96-192-5A
3 - 17
IIOIC423 Environmental Wiring Connections and Cabling
The IIOIC423 operator interface console is internally wired
when it is shipped. Connect the AC power and any peripheral
devices. The power entry panel provides line filtering, transient
suppression and a 20-amp circuit breaker.
1. Wire AC power to the proper terminals of the power entry
panel. Refer to Figure
for AC input terminal location.
NOTE: Verify that the incoming voltage meets the rating on the label
of TB1. Connect only 120/240 VAC at 50/60 hertz into the terminal
block on the power entry panel.
2. Connect only 120/240 VAC at 50/60 hertz into the termi-
nal block on the power entry panel.
3. Make certain the 120/240 VAC switch is in the proper
position.
has a list of circled cables and a description of the
cable connections. The cable connections are shown in Figure
. Circled numbers represent the cables.
Figure 3-11. IIOIC423 Environmental Cabinet Anchoring Dimensions
472.5
18.60
12.7
0.50
DIA MTG BOLTS
4 REQUIRED
SPLASH GUARDS
AIR
FILTER
430.3
16.94
711.2
28.00
707.4
27.85
MTG CTRS
MTG CTRS
TP35535B
DIMENSIONS
MILLIMETERS
INCHES