Meter Setup
Excitation Freq
[Factory Set]
A
Use Excitation Freq to configure the DC excitation of the coils . Supported frequencies are dependent on
the configured power line frequency:
50 Hz
60 Hz
1 Hz
1 Hz
3 .125 Hz
3 .75 Hz
6 .25 Hz
7 .5 Hz
12 .5 Hz
15 Hz
To change Excitation Frequency, follow these steps from the
Meter Setup
menu:
1 . Select
Excitation Freq
to view the
Excitation Frequency
display .
2 . Position the arrow to select a frequency .
3 . Press [
E
]
to save the setting and return to the
Meter Setup
menu .
Pipe Diameter
[Factory Set]
A
If the transmitter is replaced, verify that the pipe diameter matches the installed pipe size .
To change Pipe Diameter, follow these steps from the
Meter Setup
menu:
1 . Select
Pipe Diameter
to open the
Pipe Diameter
display .
2 . Position the arrow to select a diameter .
3 . Press [
E
]
to save the setting and return to the
Meter Setup
menu .
Sensor Factor
[Factory Set]
A
Use Sensor Factor to compensate for accuracy error as a result of the installed sensor . If accuracy
adjustment of the meter is required, see the scale factor parameter .
If the transmitter is replaced, this parameter must be reprogrammed with the original sensor factor .
Sensor Offset
[Factory Set]
A
Use Sensor Offset to compensate for accuracy error as a result of the installed sensor . If accuracy
adjustment of the meter is required, see the scale factor parameter .
OTE:
N
Changes of the sensor offset have an impact on meter accuracy at low flow .
Using the Main Menu Programming Options
Page 37